Home /Air Conditioners /

Enclosure Air Conditioner EA300 For Telecom Enclosure

Enclosure Air Conditioner EA300 For Telecom Enclosure

Brand Name:Coolnet
Certification:CE/ISO9001
Model Number:CJK400-600MQ
Minimum Order Quantity:1Set
Delivery Time:20-35working days
Payment Terms:T/T, L/C
Contact Now

Add to Cart

Verified Supplier
Location: Hefei Anhui China
Address: Room 303, 3rd Floor, Building C, Yingte Workshop, West Section of Yanglin Road, High-tech Zone Mechanical and Electrical Industrial Park, Hefei City Anhui Province
Supplier`s last login times: within 1 hours
Shipping
lt's easy to get a shipping quote! Just click the button below and complete the short form.
Get Shipping Quote
Product Details Company Profile
Product Details

Enclosure Air Conditioner EA300 For Telecom Enclosure


Product Introduction

Coolent is a professional thermal control solutions provider for outdoor cabinets. Coolnet has accumulated rich technological experience and lots of application in this field. The EA series is the result of Coolent technology applied in AC and DC dual powered outdoor cabinet.The cooling range is 1000~3000W, heat exchanger range is 80w/k~120w/k.


Benefits


Feature

The EA 300 is a compact, high efficient hybrid air conditioner with heat exchanger.

The design is optimized for applications with limited space available, but where functionality and performance still cannot be compromised.

Ø 220VAC for air conditioner, -48VDC for heat exchanger

Ø 3000W cooling capacity @L35L35

Ø 120w/k heat exchanger

Ø Compact design

Ø Door mounted – easy integration in outdoor cabinets and enclosures

Ø Wide working temperature range: -40ºC to +55 ºC

Ø Air conditioner and heat exchanger system as backup

Ø Energy saving, different cooling mode for varied ambient conditions

Ø Low noise, the noise level of unit can be reduced according to the heat load, silently operating in most time

Ø Lifetime >10 years – minimum maintenance

Ø Environmental friendly – R134a and RoHS compliant

Ø IP55 and Corrosion Proof

Ø Dedicated design by delay start

Ø RS485 for remote control


Application

1. Equipment cabin of Mini ICT room;
2. Equipment cabin of RRU outdoor cabinet;
3. Equipment cabin of 4G and 5G base station outdoor cabinet;
4..Equipment cabin of micro station outdoor cabinet;
5. Electric power outdoor cabinet;
6. Industrial control cabinet refrigerating;
7. Laboratory dedicated refrigerating;

Technical Specification


ModelEA-300
Power Supply( V,Hz)1P 220,50
Dimension (mm)W286
H445
D175
Cooling Capacity300W
Running Current1.48A
Starting Current6.5A
Power287W
Refrigerant TypeR134a
Noise Level55dB
Cabinet Protection Rationinternal circuitIP34
external circuitIP33
Cabinet Temperature Limits25℃~38℃(Factory Set 30℃)
Ambient Temperature Limits-5℃~43℃
Power ConnectionTriangle Power Plug( 2 Meters Length)
Weight15Kg
ColorRAL 7035(Light Gray)
Flow Rateinternal circuit70m3/h
external circuit150m3/h
Temperature Control TypeDigital Display

Test condition: dry bulb temperature inside the cabinet 35 ℃, wet bulb temperature 26 ℃;

dry-bulb temperature outside the cabinets 35 ℃