3W 3HOURS LED Emergency Pack With External LifePO4 Battery For 3 Years Warranty

Brand Name:Kreatpower
Certification:CE
Model Number:KE014-03M180HE
Minimum Order Quantity:100
Delivery Time:1, Sample and small order: Within 5 working days after receiving your payment. 2, Bulk order: 3-4 weeks after receiving deposit.
Payment Terms:T/T or Western Union
Contact Now

Add to Cart

Verified Supplier
Location: Shenzhen Guangdong China
Address: 101-1101, Building 17, Dianda Guyuan Industrial Park, Mashantou Community, Matan Street, Guangming District, Shenzhen
Supplier`s last login times: within 33 hours
Product Details Company Profile
Product Details

3W 3HOURS LED emergency pack with external LifePO4 battery for 3 years warranty


1. Description

1) Constant power output LED emergency power supply with a wide output voltage range;
2) Input; output relay switching.
3) With multiple protection functions: battery overcharge, over-discharge protection, and output short circuit protection


2. Parameters

Charge PartKE01402M/02A18003M/03A18004M/04A18005M/05A180
Rated input voltage220-240Vac 50Hz /60Hz
Rated input current0.06A Max. @230Vac
Input inrush current30A(twidth=100uS 50% Ipek@230Vac(Cold start at full load )
Power factor≥0.5@230Vac
Input power<4W
Battery charging current (Max)350mA
Battery charging time24 hours Max
Emergency PartOperating modeEmergency mode
Load typeLED
Emergency power2W3W4W5W
Emergency time3hours
Load output current100-30mA130-45mA200-65mA230-80mA
Load output voltage20-60VDC
BatteryLifePO4 (The battery capacity meets the emergency time at 25℃)6.4V 1.6Ah6.4V 3.6Ah
Battery warrantyWarranty 3 years, Design Life 5 years.
Exception Driver RequirementsSurge currentN/A
Input currentN/A
Output current2 A Max.
Emergency Function TestChargingGreenlight
FaultGreen light off
Manual testYes
Auto TestingAutotest KE014-02A180HE/03A180HE/04A180HE/05A180HE
Fault/test / StatusReasonCharge Indicator Status
Battery fully charged and operationalStandard daily usesolid green
Battery ChargingInitial Charge/Battery Top Upsolid green
Auto Test 3 Hours (every 12 months)Periodic self-testFlashing Green 3 sec on 1 sec off
Auto Test 5 Min (every 30 days)Periodic self-testFlashing Green 3 sec on 3 sec off
Duration test faultFailed the 3-hour annual testFlashing Red 0.5 sec on 0.5 sec off
LED faultNot plugged in or damaged/faultyFlashing Red 2 sec on – 2 sec off
Battery Disconnected/FaultyNot plugged in or damaged/faulty

solid red

Emergency protectionBattery over-charge/deep discharge protectionYes
Output over-voltage protectionYes
Output overload protectionYes
Output short circuit protectionYes

Operating

Environment

Operating temperature/humidity0℃…+50℃ Humidity:20%-75%(without condensation)
Storage temperature/humidity-5℃-35℃
Case Max. Temp(Tc)75℃

Safety

& EMC

Withstand voltage3000Vac 5mA 60S (Input “L N” – output “SEC+ SEC-)
Safety standardEN61347-1, EN61347-2-7
EMC standardEN55015, EN61000-3-2, EN61000-3-3
Battery standardUN38.3
Environmental protection requirementsCompliant to RoHS
CertificationCE
OthersInput/output(terminal/wiring) specificationPress terminal, wire diameter:0.5-0.75mm2
IP ratingIP20
Type of protectionClass 2
Installation typeBuilt-in installation
Installation dimension146*30*22.5mm
OthersPackaging requirementWhite box+Instruction manual+clapboard+outer carton(K=A)
Weight : Emergency Power Supply75g
Lifespan5 Year @Ta ( Battery not included )

Notes:

All parameters are tested on the input voltage 230Vac, environment temperature 25℃ unless otherwise specified.


3. Dimension (Unit:mm)

4. Wiring Diagram

5. Function


6 .Manual Test & Operation Instructions

1). Connect the wire according to the wiring diagram.
2). L, N power on, Switch on S1. then the load lamp turns on, The emergency driver indicator light turns green, emergency power supply normally charging. Turn off Switch S1, and the load lamp turns off.
3). Emergency Simulation: Switch on, the load lamp turns on, press the switch(TEST SWITCH), then switch to emergency mode, and the indicator light of the emergency driver will be extinguished. Release the switch(TEST SWITCH), then the lamp is powered by the led driver, the indicator light will turn on.


7. Battery Application Notice

1)The battery should be recharged and discharged semiannually in normal use conditions.
2)Do not connect to the circuit when the battery is not used to prevent over-discharge of the battery due to self-consumption of the circuit board.
3)Please keep the battery from the heat source when installing and using, and only be allowed to use it in a certain working temperature range.
4)The battery should be stored in a cool and dry environment.
5)After a long time of storage, the battery is cycled every 12 months as required.