High efficiency air source System heating and cooling

Brand Name:HISEER
Certification:CE / EN14511
Model Number:AW10/B-DNNNS
Minimum Order Quantity:2 pieces
Delivery Time:15-20 days after payment
Payment Terms:TT or L/C at sight
Contact Now

Add to Cart

Active Member
Location: Guangzhou Guangdong
Address: Xicheng Industry Zone, Renhe Town, Baiyun District, Guangzhou, Guangdong, China
Supplier`s last login times: within 29 hours
Product Details Company Profile
Product Details

High efficiency air source System heating and cooling

AW10/B-DNNNS, HISEER heat and cool system with stainless steel cabinet, 380-415V/3/50Hz, all year round used, energy saving heat pump: heats & cools your house as well as offers domestic hot water.

Air-source heat pump, often used in moderate climates, moves energy from the air into the building for heating or cooling and domestic hot water. Even at temperatures as low as -20˚C, an air source heat pump can supply significantly more energy than it uses – and with no local C02 emissions, it helps reduce impact on the environment.

HISEER heat pumps adopt the following world famous parts:

  • Hitachi scroll compressor
  • SWEP or GEA plate type heat exchanger
  • Siemens controller
  • Emersion thermal expansion valve
  • Emersion dry filter
  • Schneider A/C contactor
  • Honeywell R410a refrigeration

Heat pumps are measured by their coefficient of performance (COP). The COP for air source heat pumps is very similar to that for ground source heat pumps at approximately 2-4. With a COP for instance of 4, 4 units of heat are produced for every 1 unit of electricity consumed. (The three free units of heating were extracted from the outside air). Even with ambient air temperatures of -10 to -15 degrees Celsius, an air source heat pump can extract useful heat (i.e. > 1 unit of heat generated per unit of electricity consumed).


Advantages:

  • Silent operation
  • Low investment costs with high quality
  • Utilization all the year round for heating, cooling as well as hot water
  • Easy installation
  • Reducing your carbon emission
  • Enjoying your green life by installing HISEER heat pumps
  • Reducing your heating and cooling bill with high efficiency HISEER heat pumps
  • AW10/B-DNNNE technical data

AW10/B-DNNNS

AIR TO WATER HEAT PUMP

AW10/B-DNNNS

Heat output/Power consumption at 7/35℃

kW

11.0/2.9

Heat output/Power consumption at 7/45℃

kW

10.5/3.3

Heat output/Power consumption at 7/55℃

kW

10.2/4.1

Heat output/Power consumption at 2/35℃

kW

9.5/2.8

Heat output/Power consumption at 2/45℃

kW

9.2/3.4

Heat output/Power consumption at -7/35℃

kW

7.2/2.8

Heat output/Power consumption at -7/45℃

kW

7.1/3.4

Cool output/Power consumption at 35/7℃

KW

9.5/3.3

Starting current

A

46

Power

 

380-415V/3PH/50Hz

Compressor

 

HITACHI scroll

Condenser

 

Brazed plate heat exchanger

Nominal flow heating medium

l/s

0.52

Internal pressure drop at nominal flow

kPa

24

Air flow

m3/h

3000

Nominal output fan

W

220

Max outgoing heating medium temperature

55℃

Dimensions(HxWxD)

mm

1050x1050x450

Pipe connector

 

DN25

Weight

kg

125

· The above data is tested by EN14511


China High efficiency air source System heating and cooling supplier

High efficiency air source System heating and cooling

Inquiry Cart 0