IP65 Differential Air Pressure Sensor Diff Pressure Sensor For HVAC System

Brand Name:KeramControls
Certification:CE
Model Number:KDP110
Minimum Order Quantity:10
Delivery Time:7-10days
Payment Terms:T/T, L/C
Contact Now

Add to Cart

Verified Supplier
Location: Nanjing Jiangsu China
Address: Room 402, Block A, Building 12#, LianDong U Valley, No. 1 Qingnian Road, Yuhuatai District, Nanjing City, Jiangsu Province, China, 210039
Supplier`s last login times: within 27 hours
Product Details Company Profile
Product Details

differential air pressure sensor diff pressure sensor


Description


The working principle of the differential pressure transmitter transfers the differential pressure taken by the standard throttling parts (nozzles, orifice plates, venturi tubes) to the isolation diaphragm on both sides of the transmitter through the pressure pipes on both sides of the differential pressure transmitter, and then transmits the differential pressure signal to the measuring element through the sealing fluid (silicone oil, fluoro oil) in the diaphragm, and then the measuring element will convert the differential pressure signal into the corresponding electrical signal and transmit it to the converter, Finally, it is transformed into standard electrical signals (1~5V, 4~20mA) after being processed by operational amplifier and other units.


Generally, the installation site of the differential pressure transmitter is far away from the control room. In order to ensure that the signal is not distorted during transmission, the standard current signal of 4~20mA is generally used as the transmission signal, and the contact signal in the control room becomes 1~5V.


Feature


  • Ranges from -25/+25Pa to -10000/+10000Pa (according to models)
  • Auto zero manual calibration
  • Voltage, current, digital signal output
  • Standard accuracy <±1% FS
  • IP65 house protection
  • When ≤100Pa,accuracy<±3%FS±2Pa

Application


  • HVAC system
  • Pharmaceutical clean rooms
  • Electronic clean rooms
  • Medical clean rooms
  • Commercial buildings
  • Public transport hub

Technical data


ModelKDP110
Measurement UnitsPa,mmH2O,inWG,mmHG,KPa,mbar
Accuracy<±1% FS@-5 to +65℃
Response Time0.5s
Repeat Stability±0.01 % at FS /Year
Resolution0.1 Pa; 0.1 mmH2O; 0.01mbar; 0.01mmHG
MediaAir and neutral gases
Operating Temperature-20…+70℃
Storage Temperature-40…+60℃
Power Consumption<1.5W
Tolerated over pressurex15
Power Supply16~30VAC/DC (3wire) / 18~30VDC (2wire)
Output Signal4-20mA(2wire)
4-20mA(3wire)
0~5V/0~10VDC(3wire)
RS-485
Customized
Auto ZeroManual calibration
Housing MaterialPC&ABS,UL94V-0
Protection ClassIP65/NEMA4
Cable GlandM16*1.5

Dimension



Measuring range adjustment



Output setting(3 wire Model)



Manual Zero-point correction



Ordering guide


KDP110-Range-Output


ModelRangeOutput
KDP110-100~+100Pa(1)4-20mA(2 wire)(E)
-1000~+1000Pa(2)4-20mA(3 wire)(F)
-2000~+2000Pa(3)0-5/0-10V(3 wire)(G)
-10000~+10000Pa(4)RS-485(H)
Customized