Product Details

63A Residual Current Operated Circuit Breaker RCB MCB Circuit Breaker Heat Resistant


Application

The DZ47LE residual current operated circuit breaker is applicable to the circuit with an alternating current of 50Hz, rated-voltage single pole and two lines/two poles 230V, three poles/three poles and four lines/four poles 400V, and a rated current up to 63A; when the human body gets an electric shock or thenetworkleakcurrent exceeds the specified value, the residual current operated circuit breaker can rapidly cut off the power supply in trouble within a very short time for the safety of the human body and the powered equipment. With the function of overload and short circuit protection, the residual current operated circuit breaker can be used to protect the circuit or motor from being damaged by overload and short circuit, and can also be used for not–frequent operational transformation in the circuit under normal condition.The product meets the standards of IEC 61009-1.


Normal operating conditions:

1. air temperature: -5°C~+40°C, the mean value is no higher than +35°C within 24 hours .

2. Altitude: not higher than 2000m in installation site.

3. Atmospheric conditions:The air Relative humidity in the installation point will can't more than 50% in the highest temperature 40 C.

The air Relative humidity can't more than 90%, in the month most humidity and Monthly average minimum temperature not higher than 25 C.

4. Installation category: II, III grade.

5. Pollution degree: 2 grade.

6. Installation: Standard rail installation TH35-7.5 DIN rail

7. Installation conditions: Installation place of the external magnetic field in any direction should not exceed 5 times of the geomagnetic field, leakage

circuit breaker shall be installed vertically, generally handle up to position, turning on the power supply installation area should be no significant impact

and vibration.

8. Connection: screw wiring.


Model


1. Leakage circuit breaker rated connect breaking capacity


Shell Frame Rated CurrentPoleNeutral LineRated CurrentRated Short Circuit breaking capacityOver-voltage Trip
Rated Voltage(V)breaking capacityCOS
321N

6.10

16.20

25.32

22040000.7C
2
2N380
3
3N
4
321N

6.10

16.20

25.32

22040000.8D
2
2N380
3
3N
4
631N40.6022040000.8C
2
2N380
3
3N
4

2. Over-current protective feature

ItemRated Current(A)Starting StatusTest Current(A)Test TimeExpected ResultsTest TemperatureRemark
aAllCold1.13Int>1hNot trip
bAllHot1.45Int<1hTrippingUp to rated current after 5s
c<32Cold2.55In1s<t<60sTripping
>32Cold1s<t<120s
dAllCold

5In(C)

10In(D)

t>0.1hNot tripClosed auxiliary switch and connect power
eAllCold

10In(C)

14In(D)

t<0.1sTripping
fAllCold1.13Int>1hNot trip
gAllHot1.91Int<1hTrippingUp to rated current after 5s
hAllCold1Int>1hNot trip


Ordering information


Please remark these points when place the order.

A. Model .Name; eg: DZ47LE-32,Leakage circuit breaker

B. Rated Current; eg:25A

C. Pole and line number; eg: Single pole two line

D. Rated Voltage; eg:220V

E. Rated leakage circuit action current; eg:30mA

F. Quantity; eg:50pcs

Circuit breakers perform 3 key functions: protection, switching, and monitoring. Circuit breakers are designed to “break” (discontinue) the flow of electricity to protect people and equipment when current reaches an unsafe level due to overload, short circuit, or other electrical faults. We are your one source solution for all your circuit breaker and equipment needs.


Normally, we will provide the most suitable shipment method for you. If the quantity is few, the goods will be sent by express when the payment is clear. Also, we can transport the goods by air or by sea, just according to your demand


Sichuan Baikong Electrical Technology Co.,Ltd has perfect testing equipment and strict testing standards, perfect management and operation and quality assurance system. The company adheres to the enterprise purpose of synchronizing with the world and win-win with customers, adhering to scientific management, loyal to design, pioneering and innovation, and tree corporate image Business philosophy, and fully understand customer needs, do the customers think, with customers to create, win-win best control electrical staff continuously forge ahead The spirit of pragmatic innovation, serving the power construction at home and abroad to compose the new chapter The control electrical products successively in the national key projects and large enterprises are widely used, and to get the customer the consistent approval .

Sichuan Baikong Electric Technology Co., Ltd sincerely look forward to the presence and cooperation of old and new customers and win-win new future together.


China 63A MCB Circuit Breaker RCB supplier

63A MCB Circuit Breaker RCB

Inquiry Cart 0