TS100 Control Valve Volume Booster 0.4-0.7MPa Pneumatic Valve Positioner

Brand Name:Tissin
Certification:CCC,CE
Model Number:TS100
Minimum Order Quantity:1
Delivery Time:5-10 Work days
Payment Terms:L/C, D/A, D/P, T/T, Western Union, MoneyGram
Contact Now

Add to Cart

Verified Supplier
Location: Wenzhou Zhejiang China
Address: 58 Longhe Road, Liushi Town,Wenzhou, Zhejiang, China 325604
Supplier`s last login times: within 14 hours
Product Details Company Profile
Product Details

Original Tissin TS100 series Volume Booster flow amplifier,Speed up control valve device


product description

Volume Booster TS100 series products are used to speed up the control valve action device. When the flow of the valve positioner can not meet the requirements of the speed of the control valve, the flow amplifier is installed at the outlet of the valve positioner. According to the change of the pressure at the outlet of the valve positioner, the pressure of 11 will provide the air source with large flow to the actuator and improve the regulation speed of the control valve.


Features


- Adjustable Sensitivity control allows this Volume Booster to meet various control valve

requirements.


- Soft seats provide tight shut off to reduce unnecessary air consumption.


- Small size and light weight allow the Volume Booster to be installed directly inline
without a bracket.


- Options available (High and Low Temperature)


Using the environment

Do not use in corrosive environment.

When it is used beyond the normal working range, the normal service life of internal diaphragm and other parts of the product will be affected, and abnormal operation may occur. Therefore, please use it within the specified temperature parameter range.


specification

Brand nameTISSIN
ModelTS100
Signal and output pressure ratio1:1
linear1%
Air source signal interface sizePT(NPT)1/4
operating temperature range-20℃~70℃
Materialaluminium
Weight
  • 0.55kg
Maximum air supply pressure1Mpa
Output pressure range0.4~0.7MPa


To take over the way

① The outlet of the valve positioner is connected to the pressure signal interface of the flow amplifier.

② The air source output interface of the flow amplifier is connected with the air chamber of the actuator.

The air source is connected to the air source input interface.

Bracket installation Method

If a support is required, prepare the support and install it according to the following figure.


Precautions for installation and commissioning
1. For personal and system security, you are advised to install and debug the device by professional technicians.
2. When the product is used beyond the range of parameters, it will leak out due to the explosion of compressed air, causing damage to parts or personal injury. Therefore, please confirm the rated parameters of the product before installation and debugging.
3. When the product fails, in order to avoid high air pressure directly input to the actuator, the input interface must be installed with air filter pressure reducing valve to ensure the safety of the system.


China TS100 Control Valve Volume Booster 0.4-0.7MPa Pneumatic Valve Positioner supplier