Add to Cart
Dwyer 4-20mA Differential Pressure Transmitters
Product name: 616KD differential pressure transmitter
Product model: Dwyer 616KD series
Medium : Air and non-combustible gas, compatible gas
Accuracy:616KD-A: +0.25%FS:616KD-B+1%FS.616KD:+2%FS
Stability: ±1%FS/year
Temperature range: -17.8-60℃
Temperature range: -667-50℃
Pressure Range: 2 psig (range 5inw.c. or lower); 5psig (range
10-40in w.c.)
Power 4-20mA output: 10-35VDC (2 wires) or 12-26VAC (4 wires);
5V output: 10-35VDC (3 wires) or 12-26VAC (4 wires): 10V output:
13-35VDC (3 wires) or 12-26VAC (4 wires)
Output signal: 4-20mA or field selectable 0-10.0-5.2-10.1-5V
Zero and span adjustment keys
Loop resistance 4-20mA output (DC): max 0-1250QR max=50(VpsDC-10)Q:
4-20mA output (AC): max 0-12002.R max=50(1.4VpsAC-12) 2: voltage
output: 5K2 min
Current consumption: 24mA max
Warm-up time: 20 seconds
Electrical Connection: Screw Terminal
Process connection: In-line, double size can be connected to inner
diameter 1/8" and 3/16" (3mm and 5mm) rubber or plastic pipe.
Shell protection: NEMA1 (IP20)
Mounting Orientation: Perpendicular to the pressure connection
point
Features
Zero and span calibration at the push of a button, saving
installation time and extending life Cost effective, compact and
ideal for OEM applications
Wide range of ranges and accuracies to choose from for standardized
applications
Applications
Air handling unit filter monitoring, duct pressure, VAV variable
air volume
Pharmaceutical equipment/textile machinery
Product Description
The 616KD series differential pressure transmitter adopts
One-Touch? one-button digital calibration technology, which is
simple in design
Easy installation and maintenance. Ideal for professionals. Instead
of using the conventional potentiometer method for zero adjustment
and calibration, the one-button calibration technology of the word
button chain is adopted, so that both the zero and the range are
calibrated immediately, without any other calibration equipment and
tools. There is also no need for a pressure source for calibration.