IEC 60669-1 Clause 18&19 Compliant Load Cabinet 40A Output Current For Electrical Testing

Brand Name:Sinuo
Certification:Calibration Certificate (Cost Additional)
Model Number:SN2117-40A
Minimum Order Quantity:1
Delivery Time:30 Days
Payment Terms:T/T
Contact Now

Add to Cart

Verified Supplier
Location: Guangzhou Guangdong China
Address: Room 101, 1st Floor, No. 6, Third Street, Pingshan Industrial Zone 511495, Shibi Street, Panyu District, Guangzhou, China
Supplier`s last login times: within 36 hours
Product Details Company Profile
Product Details

IEC 60669-1 Clause 18&19 Compliant Load Cabinet 40A Output Current For Electrical Testing


Product Overview:


The load cabinet are designed and manufactured according to IEC 60884-1: 2022 Clause 20 &21 figure 23; IEC60669-1:2017 Clause 18 &19 and etc. It is applicable for household and similar fixed electrical installations switches and plug sockets breaking capacity and normal operation test. The purpose is assessing whether the switch is able to withstand the normal use of mechanical damage and electrical fatigue damage, and whether the contacts has adhesion phenomenon, long-term closed or disconnected phenomena, to examine whether the test samples excessive worn and have other harmful consequences.

Front top is the operator control panel, the panels are made of high quality aluminum plate, etching sandblasting colored craft, attractive and durable. There are power switch/current/voltage and power/power factor displaying instruments, load power switches, status indicators, start and stop buttons, capacitance switches, load switches and alarms etc. Below corresponds to the output voltage regulation knobs, output current regulation knobs and power factor regulation knobs. The load box has three independent stations, each with resistive, inductive load two in one feature, they are switchable. The interior of the load box is cooled by strong wind convection cooling. At the back of the load box there are wire connecting terminals, the load box outputs current voltage and power during the detection by connecting the wire with the test samples on the endurance test machine.


Technical Parameters:


Power Supply

Three-phase four-wire AC380 ± 10% / 50Hz.

Note: must have neutral wire.

Test Station3 stations, independent output
Electrical Control MethodButton control
Output Voltage0~300V, accuracy ±0.5%, digital display
Output Current0~40A, accuracy ±0.5%, digital display
Power Factor0.3~0.98, accuracy ±0.5%, digital display
Output Power0~12KW, accuracy ±0.5%, digital display
Load TypeResistive, inductive, capacitive three-in-one, switchable
Capacitive Load70uf, 140uf,7.3uf are switchable
Load OutputOptional for each load output and separate load output
Test Times0~999999 times, can be preset
Load Power Supply Capacity3*12KVA
Overrun AlarmUpper limit of output current is 40A, automatically cut off if over 42A
Dimensions & WeightApproximately:1300×900×1900(mm)W×D×H, 600kg



China IEC 60669-1 Clause 18&19 Compliant Load Cabinet 40A Output Current For Electrical Testing supplier

IEC 60669-1 Clause 18&19 Compliant Load Cabinet 40A Output Current For Electrical Testing

Inquiry Cart 0