IEC 60898-1 Clause 9.7 12.5kV Impulse Voltage Generator For MCB Test

Brand Name:Sinuo
Certification:Calibration Certificate (Cost Additional)
Model Number:SN1104
Minimum Order Quantity:1
Delivery Time:30 Days
Payment Terms:L/C, , T/T, Western Union, MoneyGram
Contact Now

Add to Cart

Verified Supplier
Location: Guangzhou Guangdong China
Address: Room 101, 1st Floor, No. 6, Third Street, Pingshan Industrial Zone 511495, Shibi Street, Panyu District, Guangzhou, China
Supplier`s last login times: within 36 hours
Product Details Company Profile
Product Details

IEC 60898-1 Clause 9.7 12.5kV Impulse Voltage Generator For MCB Test


Standards & Clauses:


The Impulse Test Generator conforms to the standard requirements of IEC 61009-1:2012, IEC 60898-1:2015 clause 9.7, IEC60335-1 clause 14, etc.The Impulse Test Generator conforms to the standard requirements of IEC 61009-1:2012, IEC 60898-1:2015 clause 9.7, IEC60335-1 clause 14, etc.The Impulse Test Generator conforms to the standard requirements of IEC 61009-1:2012, IEC 60898-1:2015 clause 9.7, IEC60335-1 clause 14, etc.


Samples and Restrictions:


It is used to verify that the Household and similar appliances, information technology equipment, audio-visual electronic equipment.


The impulse voltage tester is a standard lightning wave test device with a waveform of 1.2/50µs (10/700µs). The wave front time of the instrument is 1.2µs (10µs), and the back wave time is 50µs (700µs). The impulse voltage tester is a destructive test. In the test, if the test object cannot withstand the applied voltage, breakdown will occur. When the test product breaks down, sparks and discharge sounds will be generated, and the peak voltage of the instrument will drop significantly (close to zero) compared with the no-load condition. When the same voltage is applied to test again in the future, the above phenomenon will appear.


Technical Parameters:


Open Circuit Output Voltage12.5kV (Max) ±5%
Impulse voltage wave

Impulse Wavefront Time: 1.2 µs ± 30 %;

Half Value After Wave Time: 50 µs ± 20 %

Please note that the waveform should be checked on an external oscilloscope

Output polarityPositive, negative, positive and negative cycles
Instrument internal resistance2Ω±10%, 12Ω±10%, 500Ω±10%
Trigger methodAutomatic or manual, single trigger
Number Of Test1-9999 times
Surge Interval Time3-999s (where 3s is the inherent charging time of the device)
Mainly for samples2Ω is for the anti-interference test of indoor interconnection ports, 12Ω is for power line ports, and 500Ω is for material or component testing, mainly referring to coils
Open circuit voltage waveform

Impulse wavefront time: T1=1.67T=1.2 µs ± 30 %;

Half value of after wave time: T2=50 µs ± 20 %


Measured waveform diagram
Dimension470mm×260mm×500mm
Weight30 KG
Sample Display:
China IEC 60898-1 Clause 9.7 12.5kV Impulse Voltage Generator For MCB Test supplier

IEC 60898-1 Clause 9.7 12.5kV Impulse Voltage Generator For MCB Test

Inquiry Cart 0