3 Phase Outdoor Switch Device 12kv Pole High Voltage Vacuum Circuit Breaker Model
ZW8-12 series of high voltage outdoor switchgear is used in
three-phase AC power network of AC 50Hz, rated voltage 12KV for
breaking and closing the rural network, city network and load
current ,overload current, short circuit current for small scale
power system. The overall structure of the product for the
three-phase with whole box-type, and using the SMC insulation
materials , , and it has reliable performance, high dielectric
strength.
ZW8-12G is consist of ZW8-12 circuit breaker and isolation knife
.and it is called conbination of circuit breaker.and also can be
used segment switch,The series of ZW8-12,the mode of operation can
be divided into manual and electric.
Structural Features
Town, country reform ideal equipment: It can be set with control mechanism to remote control, remote measure and adjustment.
Flexible operation, convenient: This product has performance of
electric energy storage, electric close-open and hand energy
storage, hand close-open, it also can be operated close or far
remote.
Superior performance of open-shut: 30 times of open-shut short
current at 20kA.
Small capacity of operation and high reliability: New designed
small electric spring structure, parts numbers and operate
capacity(about 30W) can be reduced to *** level.
Maintenance-free performance: Main breaker circuit and bivariate
device, operate structure were all sealed in air of SF6(zero
pressure)and not affected by outside.
Reliable sealability: It was used of mature seal structure
technology and reliable capacity.
Special in-out line method: It was used silicon rubber pipe and
make terminals distance sufficient, good insulator outside.
Safety in use: There was explosion proof equipment set on the top
of box, even if breakdown inner, high temperature air or splash
will not out.
Note: Due to continuous product improvement, the dimensions provided in this sample are for reference only. If necessary, our company can design and produce according to user requirements. Please contact the company in time.
Item | Unit | Parameter | |||||
Rated Voltage | kV | 12 | |||||
Rated Current | A | 630 | |||||
Rated Short-circuit Breaking Current | kA | 6.3 | 12.5 | 20 | |||
Rated Short-circuit Making Current (Peak) | kA | 16 | 31.5 | 50 | |||
Rated Peak Withstand Current | kA | 16 | 31.5 | 50 | |||
Rated Short-time Withstand Current | kA | 6.3 | 12.5 | 20 | |||
Rated Insulation Level | 1min Power Frequency Withstand Voltage (Dry Test) | kV | 42 | ||||
Lightning Impulse Withstand Voltage (Peak) | kV | 75 | |||||
Rated Operating Sequence | O-0.3s-C O-180s-CO | ||||||
Mechanical Life | times | 10000 | |||||
Rated Short-circuit Current Breaking Times | times | 30 | |||||
Rated Closing Voltage of Operator | V | 110, 220 | |||||
Rated Opening Voltage of Operator | V | 110, 220 | |||||
Clearance Between Open Contacts | mm | 11± 1 | |||||
Over travel of Contacts | mm | 3 | |||||
Three-phase Opening/Closing Synchronization | ms | ≤ 2 | |||||
Closing Bouncing Time | ms | ≤ 2 | |||||
Average Opening Speed | m/s | 1.0± 0.2 | |||||
Average Closing Speed | m/s | 0.7± 0.15 | |||||
Opening Time | Highest Operating Voltage | s | 0.015~0.05 | ||||
Lowest Operating Voltage | s | 0.03~0.06 | |||||
Closing Time | s | 0.025~0.05 | |||||
Main Loop Resistance of Each Phase | μ Ω | ≤ 120 | |||||
Total Thickness of Permissible Wear of Moving and Static Contacts | mm | 3 |
· Order instructions:
1. The customer needs provide main parameters of the transformer (input and output voltage, capacity, loss, etc.)
2. Other customer requirements