Add to Cart
MV medium voltage KYN28-12 metal-clad switchgear
KYN28 indoor metal-clad withdrawable switchgear(hereinafter short as
switchgear) which is for distributing and accepting 3-phase AC
electricity (3-12 kV, 50 Hz) distribution system, single-bus and
single-bus sectionalized system. It is universally applied within
power transmission of middle/small generators in power plants;
power receiving, transmission for substations in power distribution
and power system of factories, mines and enterprises, and starting
of large high-voltage motor, etc. The switchgear compliant with
IEC298,GB3906-9. Besides, it also can control, protect and monitor
the circuit.
Simple and effective lock system to prevent misuse. Reliable
FIVE-PREVENTION interlock can effectively prevent from
mal-operation and entrance into energized compartments.
1, Prevent pushing and pulling circuit breaker handcart with loads;
2, Prevent circuit breakers from mal-operation;
3, Prevent the circuit breaker from closing and connecting when earth switch in live condition;
4, Prevent straying into electrified compartment;
5, prevent connecting error of grounding switch while live.
Perfect Removable part of the switchgear can mount with vacuum
circuit breaker and vacuum contactors components, etc.
The cabinet can debugged or maintained from front or behind, when
adopt front side for debugged,
can be installed against a wall or back-to-back be a double
arrangement, more flexible for installation and reducing floor
space.
Item | Unit | Parameters | |
Rated voltage | KV | 3, 7.2, 12 | |
Rated current | A | 630,1250,1600,2500,3150,4000* | |
Rated short circuit breaking current | KA | 25, 31.5, 40 | |
Rated short circuit switching current | 63, 80, 100 | ||
Rated short-yime withstand current(4s) | 25, 31.5, 40 | ||
Rated peak withstand current | 63, 80, 100 | ||
Rated frequency | Hz | 50 | |
Rated insulation level | 1 min power frequency withstand voltage | KV | 42 |
Lighting impulse withstand voltage | 75 | ||
control circuit voltages | AC | V | 110, 220, 380 |
DC | V | 110, 220 | |
Protection degree | Housing IP4X , cubicle and circuit breaker IP2X when door is open |