IPRU Surge Protection Device Low Voltage Components SPD 230V/400V Imax 10 20 40 65kA

Brand Name:Schneider Electric
Certification:CE,CCC
Model Number:iPRU
Minimum Order Quantity:1 Unit
Delivery Time:5-8 working days or bulk order negotiate
Payment Terms:T/T, Western Union
Contact Now

Add to Cart

Verified Supplier
Location: Wuxi Jiangsu China
Address: 606#, Building-B, 100 Dicui Road, Binhu District, Wuxi, Jiangsu, China
Supplier`s last login times: within 26 hours
Product Details Company Profile
Product Details

Schneider Electric iPRU Surge Protection Device SPD 1,2,3,4 Pole 230V/400V Home or Industrial Use Imax=10,20,40,65kA


Characteristic

  • IEC test category: Class II test (8/20us)

  • Meet the standard: GB 18802.1-2011

  • Maximum sustainable operating voltage Uc : 350 V

  • Maximum discharge current Imax : 120/100/80/65/40/20/10 kA

  • Nominal discharge current In : 60/50/40/35/20/10/5 kA

  • Voltage protection level Up: 2.5/2.2/2.1/1.9/1.7/1.45/1.2 kV

  • Number of steps: 1P/2P/3P/4P/1P+N/3P+N


Advantage

  • Complete flow capacity level to meet different location installation requirements

  • Uc (LN) reaches 350V, Uc (L-PE) reaches 440V, and the work after accessing the system is safe and reliable.

  • The full range of 1P/2P/3P/4P pole products provides phase-to-phase and neutral-to-ground common-mode protection. The full range of 1P+N/3P+N poles provides phase-to-neutral and phase-to-phase Full-mode protection from neutral to ground, suitable for grounding systems such as TT and TN

  • GB 18802.1-2011 conformity assessment, CQC comprehensive certification

  • The cooperation relationship between SPD and backup protection circuit breaker has been fully verified by Shanghai Lightning Protection Center.

Application

  • Suitable for incoming line protection, secondary protection and tertiary protection, can be used in TN-C, TN-S, TT systems


main information

Product Series

IPRU

product type

Pluggable surge protector

Product short name

IPRU 20r

Number of poles

3P + N

Output type

Remote indication signal

Surge protector application type

Power distribution network

Grounding system

TT
TN-S

Additional information

Surge protector test category

(Type II)

Structure principle and action characteristics of surge protector

MOV

Rated working voltage [Ue]

230/400 V

Maximum continuous operating voltage [Uc]

Differential mode: 350 V (L - N )
Common mode: 260 V (N - PE)
Common mode: 440 V (L - PE)

Maximum [Up] voltage protection level

Common mode <1.5 kV (N - PE)
Common mode <1.5 kV (L - PE)
Differential mode <1.45 kV (L - N )

Local signal indication

White/red mechanical indicator window

Installation type

Locking clip locking

Installation method

DIN rail mounting

Width (multiple of 9mm)

8

height

85 mm

width

72 mm

depth

64 mm

colour

White (RAL 9003)

Response time

<= 25 ns

Wiring ability

Wiring or lower wiring on tunnel terminals 2.5...35 mm2 single strand hard wire
Wiring or lower wiring on the tunnel terminal 2.5...25 mm2 cord

Recommended cable

4 mm2 fire (L)
4 mm2 zero (N)
6 mm2 ground (PE)

Tightening torque

3.5 Nm

surroundings

standard

GB 18802.1:2011
IEC 61643-1

certified product

CQC
MIIT

IP protection level

Front panel: IP40
Terminal: IP20

Operating temperature

-25...60 °C

Storage ambient temperature

-40...70 °C

China IPRU Surge Protection Device Low Voltage Components SPD 230V/400V Imax 10 20 40 65kA supplier

IPRU Surge Protection Device Low Voltage Components SPD 230V/400V Imax 10 20 40 65kA

Inquiry Cart 0