XLPE Insulated Cable for Low-Voltage Power Supply

Brand Name:HOLD-ONE
Certification:CE/IEC/KEMA/VDE
Minimum Order Quantity:Negotiable
Delivery Time:8-15 days
Payment Terms:L/C,T/T
Place of Origin:China
Contact Now

Add to Cart

Verified Supplier
Address: East of Ping'an Avenue, Jiaoxi Town, Jiaozhou City, Shandong Province
Supplier`s last login times: within 24 hours
Product Details Company Profile
Product Details

600/1000V, XLPE Insulated Cable In Accordance With IEC 60502-1


Application field


These cables are used for power supply in low-voltage installation systems and are suitable for installation in indoor and outdoor, cable ducts, underground, power and exchange stations, local energy distribution, and industrial plants without mechanical damage.


Conductor


The conductor shall be ordinary or metal-coated annealed copper or ordinary aluminum or aluminum alloy in accordance with IEC 60228 level 1 or 2, or shall be class 5 ordinary or metal-coated copper.


Insulation


The material and thickness of XLPE should meet the requirements of IEC 60502 or BS 5467, and it is suitable for continuous operation at 90°C.


Physical and Electrical Characteristics


No.cores xInsulationSheathOuter ØweightCurrent ratings in air 30℃Current ratings buried 20℃
cross-sec.thicknessthicknessapprox.approx.
Nominal
PhaseNeutralvalue
mm²mmmmmmmmkg / kmAA
3×4+1×2.50.70.71.812.72773747
3×6+1×40.70.71.813.93634760
3×10+1×60.70.71.816.15276481
3×16+1×100.70.71.818.676685106
3×25+1×160.90.71.822.21140113137
3×35+1×160.90.71.824.61475139

164


Assembly/inner cover


The inner cover can be squeezed or ground. For cables with round cores, except for cables with more than five cores, the use of overlapped inner coverings is only allowed when the gap between the cores has been substantially filled. Before applying the extruded inner cover layer, it is allowed to use a suitable adhesive. The material should be compatible with the insulating material, and the material used for the inner covering and filling layer should be suitable for the working temperature of the cable and compatible with the insulating material; for halogen-free cables, the inner covering and filling layer should also be halogen-free compounds.


Armor


According to IEC 60502-1, aluminum/galvanized steel/steel wire is spirally wound on the inner cover, and double aluminum/steel tape and copper/tinned copper wire can also be manufactured according to requirements.


Outer sheath


The outer sheath should be ST1/ST2 type extruded PVC, ST​​3/ST7 type polyethylene, halogen-free compound ST8, polychloroprene, chlorosulfonated polyethylene or similar polymers in accordance with IEC 60502-1, The SE1 type is also available on request.


Fire performance of cable sheath


The cable can be provided with a special flame-retardant PVC jacket to meet the flame-retardant test requirements of IEC 60332-3-22, IEC 60332-3-23 and IEC 60332-3-24, and the halogen-free materials comply with IEC60754-1 / 2 and IEC 60684 -2.

China  XLPE Insulated Cable for Low-Voltage Power Supply supplier

XLPE Insulated Cable for Low-Voltage Power Supply

Inquiry Cart 0