Add to Cart
Product introduction
The Transformer Fire Behaviour Test Machine is designed in
accordance with GB1094.11-2007, IEC 60076-11-2018 and other
relevant regulations.
When a certain flow of intake air is supplied to the box, 24KW
radiation illuminance is also provided for the sample. Carry out
combustion test on the transformer sample under the condition of
alcohol ignition, and record the smoke density in the smoke pipe
and the test temperature of the sample. This test equipment is
applicable to the combustion test of dry-type power transformers
(including autotransformers) with the highest voltage of 40.5KW and
below, and at least one winding is higher than 1.1kv, or
transformers involved in other relevant standards.
Reference standards:
GB1094.11-2007, IEC 60076-11-2018
Feature of chamber:
1. Dimension of stainless steel combustion test chamber 1000 ± 100
(W) × 2000 ± 100 (D) X4000 ± 100 (H) mm. The interior surface of
the chamber is higher than the ground, and the rear side is paved
with thermal insulation materials.
2. At the lower part of the box, there is an air inlet 800 ± 20 (W)
× 400 ± 10 (D) away from the front of the chamber.
3. Imported thermocouple, K-type armored thermocouple, 2mm in
diameter, is installed inside the chamber.
4. The flue at the top of the box is equipped with an anemometer to
monitor the wind speed at the outlet of the combustion chamber.
5. There is an exhaust port 300 ± 30 (W) × 1000 ± 100 (D) on the
top of the chamber, convenient for removing smoke during the test.
6. The length of air inlet duct is more than 2.6m, and the diameter
of smoke pipe is 350mm.The inlet air temperature can be controlled.
7. The Fire Behaviour Test Machine is equipped with a standard
electrical control cabinet.
8. Stainless steel smoke exhaust pipe and relevant accessories are
supplied.
Combustion system
1. Automatic electronic ignition device; It can realize remote
automatic ignition.
2. The Transformer Fire Behaviour Test Equipment is equipped with
24KW adjustable electric heating thermal radiation plate. The
radiant panel can move back and forth freely. The distance from the
sample can meet the standard requirements.
3. Radiant panel temperature can reach to 750 ° C.
4. Real time temperature monitoring in the chamber.
5. The Transformer Fire Behaviour Test Device is equipped with high
temperature alarm;
Control system
Inlet air temperature control
1. The Transformer Fire Behaviour Tester is equipped with air inlet
temperature control system. Air inlet volume 0.21 × (1±15%)m3/s.
2. The inlet air temperature shall meet the standard requirements
of 15° C~30 ° C.
3. Equipped with inlet air temperature acquisition and control
system.
4. The Transformer Fire Behaviour Test ApparatusEquipped with
imported anemometer, the system controls the inlet air volume in
real time.
5. Frequency conversion fan and imported brand frequency converter
are equipped to automatically control the wind speed.
Smoke density measurement system
1. Smoke density analysis: measure the smoke density and color
temperature 2900 ± 100K with an incandescent light system; Current
fluctuation range ± 0.5%; Smoke density value linear output with
time compensation function.
2. The lens gathers the light into a 20mm parallel beam;
d/f<0.04.
3. Photodetectors imported from the United States; The spectral
distribution correspondences are consistent with CIE; the accuracy
of chromaticity standard function is ± 5%; the output linearity is
within 3% of the light transmittance or 1% of the absolute light
transmittance.
4. 90% response time of the system shall not exceed 3s.
Computer test system
1. Standard control cabinet, computer+Labview intelligent control
system.
2. The experimental data is stored automatically and can be queried
freely; The test report can be printed freely.
3. The Transformer Fire Behaviour Test Chamber is equipped with
automatic air inlet control and wind speed acquisition system.
4. Equipped with exhaust duct wind speed acquisition system. The
exhaust fan can realize automatic smoke exhaust with large air
volume after the experiment.
5. Labwiew control system dedicated to experimental instruments,
with friendly interface, easy operation and accurate control;
Capable of: displaying instrument status; Calibrate instruments and
store calibration results; Collect test data; Calculate the
required parameters; Display the results according to the standard
requirements; Average of multiple tests.
6. Data acquisition: real-time digital display and curve screen
display of monitoring data (temperature, flow, differential
pressure, light transmittance, etc.). The test report module has
powerful functions and can preview, edit and generate reports.