Dielectric Oil Power Factor Tester Loss Tangent Meter IEC 61620

Brand Name:AI
Certification:ISO
Model Number:DFT
Minimum Order Quantity:1 Set Dielectric Oil Power Factor Tester
Delivery Time:15 days
Payment Terms:T/T, Western Union, L/C
Contact Now

Add to Cart

Verified Supplier
Location: Changsha Hunan China
Address: Hi-tech Developing Industrial Area, Liuyang City,Changsha,Hunan Province,China
Supplier`s last login times: within 30 hours
Product Details Company Profile
Product Details

Dielectric Oil Power Factor and Loss Tangent Meter


I. Introduction:

Automatic Dielectric Oil Power Factor and Loss Tangent Meter is a high-precision instrument, which can be applied to measure dielectric loss angle and Volume Resistivity of insulating oil etc.

This dielectric loss tangent meter is integrated with oil cup for dielectric loss, temperature-control equipment,temperature sensor, test-bridge for dielectric loss, AC trial electrical source, standard capacitor,high resistance meter and DC high-voltage power etc.
The most advanced heating mode of high frequency induction is applied to the heating part of this dielectric oil power factor tester, which has the advantage of non-contact of oil cup and heating unit, homogeneous heating, quick velocity and convenient control etc. AC-DC-AC conversion mode is applied to AC trial electrical source so that the problem how to measure correctly under the fluctuation of voltage and frequency can be avoided. Even when the electric generator is working, the transformer oil volumn resistivity tester can operate correctly.
The inner standard capacitor is SF6 three-pole inflate capacitor, whose dielectric loss and capacitance is not influenced by environmental temperature and dampness etc. In this way, the accuracy of insulation oil dielectric loss tangent meter is guaranteed conformably after a long-time application.

II. Specifications:

Condition of Use-5℃-40℃ RH<80%
Power SourceAC 220V±10% Without Frequency Limit
AC High Voltage Output400V-2200V ±2% Every 100V 50VA
DC High Voltage Output200V-600V ±2%
Temperature Control Induction StoveMaximal Power 500W
Temperature Control Range<100℃
Temperature Measuring Error±0.5℃
Control Temperature Error0.1℃
Control Temperature TimeRoom Temperature 90℃ <20min

Measuring Range

tgδ Without Limit

Cx 15PF-300PF

Rx 10M-10T

Resolution

tgδ 0.001%

Cx 0.01pF

Rx 0.01

Precision

delta tgδ:±(Reading*0.5%+0.020%)

delta Cx :±(Reading*0.5%+0.5PF)

delta Rx :±Reading * 10%

Relative Dielectric Loss ConstantΕr Calculated Automatically
Volume Resistivityρ Calculated Automatically
Dimension450(L)×310(W)×360(H)
Net Weight21KG