I. Introduction:

Insulating oil in electrical power apparatus serves two primary roles, as an insulator and a coolant. As an insulating liquid, oil’s most important property is a high dielectric strength and as a cooling liquid, a low viscosity is paramount. The principal nemeses of insulating oil are oxidation, contamination (particularly moisture, which tends to lower the dielectric properties of insulating oil), and excessive temperature. These enemies are managed through design, regimented installation processes and prudent operation of the oil-filled power apparatus. At all stages of a power asset’s life, testing must be conducted to evaluate the condition of the insulating oil. In fact, for some assets, it can be argued that the oil is tested more frequently than any other component.


Tests that are concerned with the immediate condition and acceptability of the insulating oil include dielectric breakdown tests, moisture measurement by the Karl Fischer (KF) method, and dielectric dissipation factor.


II. Functions:

  • Breakdown test of user-defined

  • Proof test

  • Calibration interface for customers

  • Uploading data to PC and making word report automatically.

  • Result print


III.Specifications:

1Output voltageAC 0~80KV
2Rate of voltage rise2KV/s±10%
3Measuring precision3%RDG+0.3%FS
4Test times setting1-9
5Mixi time settingng0~99 second Waiting time setting: 0-9 minute 59second
6Maximum storage capacity100 groups of test data
7Display256´128 LCD
8Power supplyAC220V±10%, 50Hz/60Hz
9Working environment0-50℃, ≤80%RH
10Test standardIEC60156