1. Description

CKFL SF6gas-insulated switchgear is a completely sealed & insulated medium voltage ring main unit working in a voltage range maximum up to 24kV.

2. Technical Feature

---- Flexible expansion

---- Rustproof cabinet with high mechanical strength

---- Safe & reliable gas tank

---- Spring operating mechanism with anti-misoperation system

---- Fuse with sealed isolation

---- Simply and convenient connection

3. Working Condition

3.1 Altitude:≤1500m

3.2 Ambient air temperature: -35℃~+40℃

3.3 Max. average daily temperature: +40℃ Max. annual average temperature: +35℃

3.4 Wind speed: ≤34m/s

3.5 Relative air humidity: ≤90% ( +25℃)

3.6 Ground gradient: ≤5°

3.7 Earthquake intensity: ≤magnitude 8

3.8 Applicable in the places without fire, without explosion risk, without chemical corrosive and without violent vibration

(Exceeding above working condition is available as customized product)


4. Technical Data


Technical DataUnitModule CModule FModule V
Load switchSwitch-fuse combinationVacuum switchDisconnector/ earthing switch
Rated voltagekV1224122412241224
Rated frequencyHz50505050
Rated currentA630125630630
Rated breaking cable charging currentA2020//
Rated short-circuit making current(peak)kA50Up to fuse50405040
Rated short-circuit breaking currentkA/Up to fuse2016//
Rated short-time withstand currentkA20/20162016
Rated short-time withstand current duration(main circuit)s4/4444
Rated short-time withstand current duration(ground loop)s2///
Rated breaking transfer currentA/1600//
Rated short-time power frequency withstand voltagephase-to-phase phase-to-earthkV/1 min4250425042504250
open contactkV/ 1 min4865486548654865
Rated lightning impulse withstand voltagephase-to-phase phase-to-earthkV7595759575957595
open contactkV85110851108511085110
Mechanical lifetimes5000500050005000
Mechanical life of earthing switchtimes≥2000≥2000≥2000≥2000
SF6 pressure in seal enclosureMpa0.040-0.0450.040-0.0450.040-0.0450.040-0.045
SF6 annual leakage rate/≤0.02%≤0.02%≤0.02%≤0.02%


5. Available modules options

● CKFL- □ / C-----Load switch module

● CKFL- □ / F-----Switch-fuse combination module

● CKFL- □ / V-----Vacuum-circuit breaker module

● CKFL- □ / D-----Direct incoming/outgoing cable module

● CKFL- □ / CL-----Busbar sectionalizer module(load switch)

● CKFL- □ / CvKr-----Busbar sectionalizer module(vacuum switch)

● CKFL- □ / PT-----Potential transformer module


6. Standard

---- IEC62271-1