

Add to Cart
Overhead Line Transmission Acsr Dog Conductor Medium Voltage
Used as bare overhead transmission cable and as primary and
secondary distribution cable.
ACSR offers optimal strength for line design. Variable steel core
stranding enables desired strength to be achieved
withoutsacrificing ampacity
Service Performance:
(1). The permissible long-time operating temperature for aerial
conductor is 70℃.
(2). Under the circumstance that rare climate is occurring and ice
coverage rate low in heavy ice area, the biggest stress of cable at
the lowest point of the sag should not exceed 60% of the short-time
destructive power.
(3). When connecting conductors, the conductor beside the
connecting tube cant be prominent. Otherwise, the force on the
operating conductors will be unbalanced. After connectors are
install, the connecting tube should be painted by moisture-proof
varnish in order to protect it from corrosion.
(4). Under installation, the arc downing stress of all the
conductors should be the same. With in the permissible distance of
crossing buildings or dropping to the ground, the stress can be
10-15% higher than regular stress.