Product Details

1. LW-126kv 132kv 145kv sf6 circuit breaker 2150A Sulfur hexafluoride circuit breaker


Lw-126kv circuit breaker which is outdoor type finds its universal range of applications for the electrical system with elevation not greater than 2000m,ambient temperature not lower than -30℃,dirtiness grade not high than IV, alternating current 50Hz and the maximum voltage 126kV. It is used for cutting the rated current, malfunction current or switching the circuitry, to control and protect the electrical system ,and it can also be used for connecting with the circuit breaker.

The gas of the SF6 is employed as the arc-extinguishing medium and the dielectric material. The self-extinction technology and the new-type spring operating mechanism are introduced in the SF6 circuit breaker. Thus the circuit breaker has good qualities with long electrical life, low operation power, lower noise, high reliability, simple structure, small and long overhaul periods. It can fully replace the same type one.

2. Data list OF LW-126kv 132kv 145kv SF6 Circuit breaker


NoNameUnitValue
1Rated voltagekV252
2

Rated power frequency

withstand voltage (1min)

To earth460
Between interrupter460+146
3

Rated thunder impulse

withstand voltage

To earth1050
Between interrupter1050+206
4Rated frequencyHz50
5Rated currentA4000
6Amplitude factor1.3
7Rated short-circuit breaking currentkA50
8Rated short-circuit making current(peak)kA125
9Rated current withstand currentkA50
10Rated peak value withstand valuekA125
11Rated short-circuit durations3
12Rated out-of-phase breaking currentkA12.5
13Breaking current of close-in faultkA90%lk,75%lk
14Rated line-charging breaking currentA200
15Operating sequenceO-0.3s-CO-180s-CO
16Resistance other main circuitμΩ≤55
17Rated gauge pressure of SF6(20℃)Mpa0.6
18Minimum functional gauge pressure(20℃)Mpa0.550.015/0.50.015
19Annual leakage rate of SF6≤0.5%
20Amount of water of SF6(V/V)ppm≤150
21Mechanical lifetimes6000
22Electrical level of radio interferenceμV<500
23Creepage distanceTo earthmm≥8660
Between interrupter≥6900
24Weight of the SF6kg24
25Weight of the circuit breakerkg1500

3. working Conditon of LW-126kv 132kv 145kv SF6 Circuit breaker


Surrounding air temperature: -40 ºC ~+40 ºC ;
The wind speed is not bigger than 34m/s;
The air filthy should be with in III degreealtitude above sea level does not over 2,000 meters;
Installing places: Not flammable, the explosion hazard, chemistry corrode place;


4. Technical diagram of LW-126kv 132kv 145kv SF6 Circuit breaker



5. Factory



6. Delivery



7. FAQ


1.Generally we promise one - two years quality guarantee, some products will be extended longer time for life span.

2. For tender cooperation, it is welcome to discuss the detail in between.

3. Some type reports are provided accordingly.

4. Our factory is 250000m2 for production and office.

5. There are four subsidies in our group company. So our whole group company can produce switchgear, power transformer, load break switch, disconnect switch, vacuum/sf6 circuit breaker, fuse, surge arrester, CT PT, Metering unit.