Home /

Remote Monitoring 48VDC RS485 Module Rectifier Module Telecom

Remote Monitoring 48VDC RS485 Module Rectifier Module Telecom

Brand Name:ESTEL
Certification:ISO
Model Number:GPE48120E
Minimum Order Quantity:1 set
Delivery Time:20 days
Payment Terms:L/C, T/T,
Contact Now

Add to Cart

Verified Supplier
Location: Shenzhen Guangdong China
Address: Building 3, Second Industrial Zone, Guangming Road, Shiyan, Bao'an District, Shenzhen, Guangdong, China
Supplier`s last login times: within 24 hours
Shipping
lt's easy to get a shipping quote! Just click the button below and complete the short form.
Get Shipping Quote
Product Details Company Profile
Product Details

48VDC Telecom Power Supply Rectifier 120A 6400W

Four 30A Rectifier Module Hot Pluggable Ethernet RS485


Model: GPE48120E


Introduction


Embedded DC Power provides stable -48V DC power for wireless and fixed access networks, transmission networks and enterprise network equipment. It consists of a power distribution unit, rectifiers, and a controller, etc., and can be deployed independently or embedded into other power cabinets.


Every functional unit is designed to a standard size. The systems, whose height ranges from 2U to 9U with standard 19-inch rack or cabinet installation, have a modular design to facilitate installation and expansion. The system encompasses a wide range of AC input voltage, with accurate battery management and remote management functions.


GPE48120E System Configuration


GPE48120E consists of power distribution unit, rectifier module (from 1 set, up to 5 sets) and 1 monitoring module. The configuration is optional, as following table:


ConfigurationRectifier ModuleMonitoring ModulePower DistributionRemark
StandardGPR4830A1GPM48R (With Ethernet Port)

AC power distribution: AC breaker(63A) and wire connection terminal;

DC power distribution: 100A×2 1P

LVLD: 63A×1 1P, 32A×4 1P

LVBD: 20A× 2 1P

For details, please refer to the specifications of modules.

GPE48120E Operating Principle

AC power is first input AC-INPUT MCB and then feed into the rectifier module after lightning proof and filtering. AC-INPUT acts as protection to over load and short circuit to AC power. The user’s battery is connected to the DC output side through battery MCB and KM2, and the circuit breaker provides disconnection control, over-load and short-circuit protection to the battery.

Under normal conditions, every parameter of rectifier modules and power distribution unit are all under control of the monitoring module, operating according to the pre-set parameter or user’s commands. If AC mains faults, the battery will power to the system. With the battery discharge, the terminal voltage of the battery starts to descend. When battery voltage is under -47V±0.5V, the monitoring module sends DC under voltage alarm signal and when battery voltage is under -46.0V±0.5V (adjustable), the KM1cuts off non-priority loads and retains power to priority loads. If battery voltage drops to -43.0V±0.5V (adjustable), the KM2 will cut off output of priority loads and then the power system will stop working. If the external AC mains recovers, the system will normally work again. (All above monitoring data are system default values and can be reset by user).


Except for battery over-discharge protection, battery or load over-temperature protection is prohibitive under default, users can send command to activate or inactivate according to the demanding.


System Specifications


Input
ItemMin.TypicalMax.UnitRemark
Input voltage range90220280Vac
Input frequency455065Hz
Max. Input current20A
Power factor0.99Rated load
Input over voltage protection point285VacAutomatically recoverable
Input over voltage recovery point280VacBacklash ≥5V
Input under voltage protection point85VacAutomatically recoverable
Input under voltage recovery point90VacBacklash ≥5V
Input over current protectionAC input side includes MCB for protection.

Output (Table 1)
ItemMin.TypicalMax.UnitRemark
Output voltage4253.558VdcAdjustable by monitor, tested in no load
Output power6400W176~280VAC (rated power includes battery charging power plus load power)
3200W90~175VAC input
Output over voltage protection point58.561.5VdcLock up
Output current limiting protection pointOutput current limiting protection
Output short circuit protectionLong-term short circuit protection, automatically recoverable
Over temperature protectionAutomatically recoverable in ambient temperature lower than 65°C
Battery power-down protectionBattery power-down protection
Battery polarities reversal connection protectionNo damage on battery and power system
Voltage regulation accuracy±1%

Output (Table 2)
ItemMin.TypicalMax.UnitRemark
Temperature coefficient±0.2‰/°C
Current sharing unbalance±5%Within 50~100% load range
Start-up/shut-down overshoot range±5%Any module is removed when operating, (the load current should be less than total output current of working rectifier modules), the system output voltage fluctuates
Dynamic response recovery time200uS

25%~50%~25% load variation

50%~75%~50% load variation

Dynamic response overshoot±5%Rated output voltage, rated load current
Efficiency9091%220Vac input, rated output voltage, rated load current
83%110Vac input, rated output voltage, rated load current
Start-up time38Spre-current limiting is fitted with start-up output between rated start up input voltage and rated output voltage established period
Peak-peak noise voltage200mV

Mechanical Specifications


Mechanical specifications
Dimensions (mm)as the following diagram
Weight(kg)

≤18kg (Inclusive of module)

≤10kg (Frame + Distribution, exclusive of module)



Electrical Connection


Chassis connects with external electric through system interface board. As shown in figure below:



Power Distribution Instruction:

  1. Grounding bar
  2. AC input terminal
  3. AC MCB
  4. AC SPD
  5. LVLD (5 MCBs)
  6. LVBD (2 MCBs)
  7. Monitoring module slot
  8. Rectifier module slot
  9. Module anode and battery anode copper bar
  10. Battery MCB

GPE48120E Distribution Frame