800V DC Surge Protector 2P Replace Type DIN 43880 40kA

Brand Name:FEEO
Certification:CE TUV
Model Number:dc spd
Delivery Time:15work days
Payment Terms:L/C, D/A, D/P, T/T, Western Union, Western Union, MoneyGram
Place of Origin:CHINA
Contact Now

Add to Cart

Active Member
Address: Keaisi Road, Xiangyang Industrial zone , Yueqing, Zhejiang,China.
Supplier`s last login times: within 48 hours
Product Details Company Profile
Product Details
ModelFSP-D40
UC (V DC)600/800V
Max System Discharge Current (8/20 μs) [Imax]40kA
Voltage Protection Level [UP]≤2.5kV
Integrated Fuse Breaking Capacity/Interrupting Rating40kA/600Vdc
TechnologyShort-Circuit Interruption (SCI) Overcurrent Protection
Operating Temperature Range [TU]-40°C to +80°C
Nominal Discharge Current (8/20 μs) [(DC+/DC-) --> PE] [n]20kA
Response Time [tA]<25ns
Operating State/Fault IndicationGreen (good)/Red (replace)
Conductor Ratings and Cross-Sectional AreaMin
MountingMax60/75°C 1.5mm2/14AWG Solid/Flexible
35mm DIN Rail per EN 6071560/75°C 35mm/2AWG Stranded/25mm2/4AWG Flexible
Enclosure MaterialUL 94V0 Thermoplastic
Degree of ProtectionIP20
Capacity3 Modules, DIN 43880
Standards InformationIEC 61643-31 Type 2, IEC 61643-1 Class II
Product WarrantyTwo Years**

1) Selection of voltage protection level (UP)

The value of UP should not exceed the rated value of the impulse withstand voltage of the protected equipment, and UP requires that the insulation of the SPD and the protected equipment should be well matched.

In the low-voltage power supply and distribution system, the equipment should have a certain ability to withstand surges, that is, the ability to withstand impulse overvoltage. When the impulse overvoltage withstand voltage of various equipment of 220/380V three-phase system cannot be obtained, it can be selected according to the given index of IEC 60664-1 and GB 50057-1994 (2000 edition).

2) Selection of nominal discharge current In (impact current capacity)

The peak current of the 8/20 μs current wave that flows through the SPD. It is used for class II classification test for SPD, and also used for pretreatment of class I and class II classification test for SPD.

In fact, In is the maximum peak value of the inrush current that the SPD can pass the specified number of times (generally 20 times) and the specified waveform (8/20 μs) without substantial damage.

3) Selection of the maximum discharge current Imax (limit impact current capacity)

The peak current flowing through SPD, 8/20 μs current wave, used for class II classification test. There are many similarities between Imax and In. They both use the peak current of 8/20 μs current wave to do Class II classification test on SPD. The difference is also obvious. Imax only does one impact test on SPD, and SPD does not undergo substantial damage after the test; while In can do 20 such tests, SPD cannot have substantial damage after the test. Therefore, Imax is the current limit value of the impact, so the maximum discharge current is also called the limit impact current capacity. Obviously, Imax>In.


China 800V DC Surge Protector 2P Replace Type DIN 43880 40kA supplier

800V DC Surge Protector 2P Replace Type DIN 43880 40kA