Petrochemical Plant 12 AWG 480V Electric Heat Tracing

Brand Name:MICH
Certification:ISO9001
Model Number:EHTTSORP
Minimum Order Quantity:1 meter
Delivery Time:in one month
Place of Origin:China
Contact Now

Add to Cart

Verified Supplier
Address: 1200 N Fuxing Rd Wutong Dist Tongxiang 314500 Zhejiang P. R China
Supplier`s last login times: within 1 hours
Product Details Company Profile
Product Details

Electric Heat Tracing Technical Solution for Oil Refinery and Petrochemical Plant is the technical solution package to be applied on the refinery and petrochemical plant for heat trace the instrumentations and equipments. In general, electric heating designer and manufacturers suggest that users should provide detailed working conditions and requirement when selecting the type. Once the suitable heat trace is selected, designed, manufactured and installed, the whole electric heating scheme can ensure the smooth operation of the relevant refining facilities under various working conditions.


Electric heating of air separation instrument in phase I project of 40 million tons/year refining and chemical integrated project of zhejiang petrochemical co., LTD adopts self-limiting temperature electric tracing belt and MI armored heating cable.


Self-limiting temperature electric tracing belt is a new generation of strip constant temperature electric heating products, automatically limit the heating temperature, and automatically adjust the output power with the temperature of the heat tracing body; It can be arbitrarily cut or lengthened within a certain length range.Allow multiple overlapping without the risk of high temperature overheating and burning; Easy maintenance and energy saving.

MI heating cable is made of single or multiple alloy electric heating wire as heating source, high purity, high temperature, electric melting crystallization magnesium oxide as thermal insulation, seamless continuous stainless steel or copper tubes as sheath, using special production process. Used in highly corrosive places, PE or low smoke halogen-free coat should be added to the original cable. Its advantages are excellent mechanical strength and corrosion resistance.


Table 2 Heating Cable Specification (600V Single Conductor)


Cable CodeDiameterHDPE DiameterStandard resistance value at +20Maximum Production LengthUnit weight
mmmmΩ/mmkg/km
16C1.78.2100.0017350366.54
16C2.27.69.40.0022380307.77
16C2.97.08.80.0029400264.45
16C45.97.70.004600190.88
16C75.37.10.007600154.08
16C114.96.70.011600132.25
16C134.66.40.013600 (300)☆125.7
16C174.66.40.017600 (300)☆117.16
16C214.66.40.021600 (300)☆111.9
16C253.75.50.025600 (480)☆68.83
16C333.75.50.033600 (480)☆63.76
16C403.45.20.04600 (560)☆58.87
16C633.250.06360051.47
16K806.88.60.08370 (140)☆254.18
16K1005.270.1450 (240)☆162.11
16K1404.96.70.14600 (270)☆122.55
16K1974.456.250.197600 (330)☆111.32
16K2204.56.30.22600 (330)☆102.89
16K3154.36.10.315600 (350)☆91.44
16K3454.26.00.345600 (370)☆85.9
16K4504.05.80.45600 (400)☆80.73
16K6304.05.80.63600 (400)☆77.26
16K8003.55.30.8600 (530)☆61.48
16K12502.84.61.2560040.83
16K20002.84.62.060038.96

Table 3 Heating Cable Specification (600V Double Conductors)


Cable CodeDiameterNominal resistance at +20Maximum manufacturing lengthUnit weight
mmΩ/mmkg/km
26C3.412.90.0034150783.76
26C4.412.20.0044160701.56
26C5.811.30.0058170606.16
26C8.69.900.0086180451.43
26C11.49.300.0114200400.05
26C13.89.000.0138210375.20
26C17.28.600.0172220344.90
26C238.000.023250303.25
26C34.47.500.0344280269.20
26C49.27.100.0492300243.84
26K2409.900.24180451.43
26K3209.300.32200400.05
26K3849.000.384210375.20
26K4808.600.48220344.90
26K6408.000.64250303.25
26K9607.500.96280269.20

Table 4 Heating Cable Specification (300V Double Cores)


Cable CodeDiameterNominal resistance at +20Maximum manufacturing lengthUnit weight
mmΩ/mmkg/km
23C3.412.00.0034200708.10
23C4.411.30.0044220629.07
23C5.810.40.0058240537.73
23C8.69.000.0086260392.56
23C11.48.400.0114280343.89
23C13.88.000.0138300314.57
23C17.27.600.0172320286.27
23C237.100.023340252.98
23C34.46.600.0344360221.19
23C49.26.200.0492380197.64
23K16010.40.16220508.37
23K2409.000.24240392.56
23K3208.400.32265343.89
23K3848.000.384280314.57
23K4807.700.48300291.91
23K6407.100.64320252.98
23K9606.500.96350216.11

Note: the resistance value of 2-core cable in the above table is the measured value after the ends are twisted (i.e., single-core resistance X2);

For the use of 660V voltage occasions, please contact our company professionals;

Mark of (300)☆ is a recommended production length by MICH


Selection Parameters:


Constant Wattage Heating CableHigh Temperature Heating cablePolyamide/Fiberglass Heating CableHarsh Environment Heating CableGeneral Purpose Heating Cable
Available Voltages120, 208, 240, 277 & 480 VAC120, 208, 240, 277 & 480 VAC120, 208, 240, 277 & 480 VAC120, 208, 240, 277 & 480 VAC

Available Wattages


4, 8 & 12 watts/ft (13, 26 & 39 watts/m)4, 8 & 12 watts/ft (13, 26 & 39 watts/m)4, 8 & 12 watts/ft (13, 26 & 39 watts/m)3, 5, 8 & 12 watts/ft (10, 16, 26 & 39 watts/m)
Maximum Exposure Temperature

500°F (260°C)


500°F (260°C)


500°F (260°C)


400°F (204°C)


Nominal Dimensions


0.2"x0.3" (5mm x 8mm) 12 AWG


0.2"x0.3" (5mm x 8mm) 12 AWG


0.2"x0.3" (5mm x 8mm) 12 AWG


0.2"x0.3" (5mm x 8mm) 12 AWG
Resistance to MoistureGoodGood

Excellent


Excellent


Resistance to ChemicalsGoodGood

Excellent


Excellent


Resistance to FlameExcellentOutstandingExcellentOutstanding
Dielectric StrengthOver 2000 volts

Over 2000 volts


Over 2000 voltsOver 2000 volts
China Petrochemical Plant 12 AWG 480V Electric Heat Tracing supplier

Petrochemical Plant 12 AWG 480V Electric Heat Tracing

Inquiry Cart 0