Fixed Type 205 Phase Spacing VCB Circuit Breaker Environmental Protection

Brand Name:KNKONG
Certification:CB,ISO,IEC
Model Number:VS1-12
Minimum Order Quantity:1
Delivery Time:15 working days
Payment Terms:L/C, T/T, Western Union
Contact Now

Add to Cart

Active Member
Location: Zhengzhou Henan China
Address: No. 25 Street , Hanghai Road, Zhengzhou,Henan,China
Supplier`s last login times: within 11 hours
Product Details Company Profile
Product Details

VS1-12 fixed type 205 phase spacing Vacuum Circuit Breaker 12KV 630A

Voltage: 12KV

Current: 630A

Breaking current: 20KA

Type: Fixed


Product overview

VS1-Series circuit breakers are complete independently developed by Knkong based on the advanced design concept; it adopts a modularized mechanism, which is easy for installation, maintenance, testing, and operation. As compared with conventional VS1 circuit breaker. it features higher operation stability, higher safety, and extended service life. The product can satisfy customers demand application in 12kv and 24kV power transmission and distribution systems, which is extensively applied in such industries as power, energy, petrochemical engineering, metallurgy, manufacture, traffic, building, and environmental protection as well as large-scale enterprises and national key projects


Technical Parameters

No.ItemUnitParameter
1Rated voltageKV12
2Rated frequencyHz50/60
3

Rated insulation level

1min power frequency withstand voltage(r. m. s)

KV

42(phase-to-phase, phase-to-earth)

48(across the isolating distance)

Lighting impulse withstand voltage (peak)

75(phase-to-phase, phase-to-earth)

85(across the isolating distance)


4


Rated current


A

63063012501600
1250125016002000
20002500
25003150
4000
5Rated short-circuit breaking current

KA

202531.540
6Rated short-time withstand current202531.540
7Rated short-circuit marking current506380100
8Rated peak withstand current506380100
9Rated duration of short-circuits4
10Rated operating sequenceO-0.3s-O/C-180s-O/C
11Breaking times of rated short-circuit currentTimes30/20 times(40KA)
12Mechanical enduranceOps20000
13Rated single capacitor bank breaking current

A

630
14Rated back-to-back capacitor bank breaking current400
15Double-earth fault breaking current27.4
16Allowable maximum contact erosion

mm

3
17Clearance between open contacts10±1
18Over stroke3.5±0.5
19Non-simultaneity of 3-phase opening and closing

ms


≤2
20Bounce duration of contact closing≤2
21Average breaking speed (instant breaking 6mm)

m/s


1.1±0.2
22Average making speed0.8±0.2
23Making time

ms


≤100
24Breaking time≤50

25


Resistance of each phase main circuit


μ Ω

630A≤50
1250A≤45
1600A~2000A≤35
≥2500A≤25
26Contact breaking bounce amplitudemm≤2

27

Rated operating voltageRated operating voltage(V)AC/DC

V

24*110220
Scope of normal operation voltageOpening:65%-120% rated voltage, in case the voltage is lower than 30% rated voltage, opening operation is not allowed
28Rated voltage of energy storage motorVAC110/220,DC110/220
29Energy storage timeS≤15

Operation safety

The circuit breaker has anti-mis-lock protection and "5 guarantees" interlocking function to avoid misoperation and protect the personal safety of operators to the greatest extent.
Only when the circuit breaker and the grounding switch are in the off position, the circuit breaker cart can roll from the test position to the service position
The circuit breaker can only be closed in the service/test position.
After the circuit breaker is closed, the truck cannot be rolled in or out, only when the circuit breaker is in the open position.
The circuit breaker cannot be rolled out from the service position to the test position in the closed position.
The circuit breaker cannot be closed when pushed in.
When the circuit breaker is closed, if the closing signal is not released in time, the internal anti-trip control circuit will cut off the closing circuit to prevent multiple reclosing (optional).
If electric closing and locking is selected, when the secondary circuit cannot provide power or the power provided cannot satisfy the normal operation of the locking electromagnet (optional), the circuit breaker will not be closed.