Add to Cart
Minimum impact on supplies easy sources:
Input current distortion <4% for the ZGD330 with filter with
sinusoidal absorption to remove the risk of resonance with other
input supply users or phase shift capacitor sets. The absorbed
current distortion is independent of input supply parameters such
as impedance. This enable ZGD330 to deliver maximum performance
levels regardless of the installation environment. With these input
features ZGD330 can achieve significant savings in terms of sizing
and power supply sources isolation transformers and generators over
less sophisticated power systems.
Model power | ZGD330 10-200KVA | |||||||||||
10KVA | 15KVA | 20KVA | 30KVA | 40KVA | 60KVA | 80KVA | 100KVA | 120KVA | 160KVA | 200KVA | ||
Capacity | 8KW | 12 KW | 16 KW | 24 KW | 32 KW | 48 KW | 64 KW | 80 KW | 96KW | 128 KW | 160 KW | |
Input | ||||||||||||
Rated voltage | 380/400/415 Vac three-phase | |||||||||||
Voltage range | ±20% | |||||||||||
Frequency range | 45-65Hz | |||||||||||
Power factor | >0.92with harmonic filter | |||||||||||
Current harmonic distortion | <5%with harmonic filter | |||||||||||
Soft Start | 0-100% in10" | |||||||||||
Bypass Input | ||||||||||||
Rated voltage | 380/400/415 Vac three-phase | |||||||||||
Permitted voltage range | ±15%(selectable from ±10% to ±25% from front panel) | |||||||||||
Rated frequency | 50/60Hz | |||||||||||
Permitted frequency range | ±2%(selectable from ±1% to ±5% from front panel) | |||||||||||
Standard features | Back Feed protection; split bypass line | |||||||||||
Batteries | ||||||||||||
Type | Maintenance-free lead-acid VRLA AGM / GEL;NICd | |||||||||||
Battery voltage | 384VDC | 480VDC | ||||||||||
Maximum recharge current(A) | 0.2×C10 | |||||||||||
AC ripple voltage | <1% | |||||||||||
Inverter Output | ||||||||||||
Number of phases | 3+N | |||||||||||
Rated voltage(V) | 380Vac | |||||||||||
Regulation of the output voltage | 380~424Vac phase/neutral(from control panel) | |||||||||||
Crest factor (Ipeak / Irms) | 3:1 | |||||||||||
Static stability | ±1% | |||||||||||
Dynamic stability | ±5% | |||||||||||
Frequency | 50/60Hz configurable | |||||||||||
Overload | 110% 125% 150% of the rated current for 5h/10'/1' | |||||||||||
Frequency stability | ±0.05% on mains failure;±2%(selectable from ±1% to ±5%)with mains supply present | |||||||||||
Remote signaling | Volt free contacts | |||||||||||
Remote controls | EPO and Bypass | |||||||||||
Communication | RS232 + romote contacts | |||||||||||
Operation temperature | 0ºC/ + 40ºC | |||||||||||
Relative humidity | <95% non condensing | |||||||||||
Noise | 54dBA at 1m | 50-65dBA at 1m | ||||||||||
Protection degree | IP20 | |||||||||||
Efficiency smart mode | up to 98% | |||||||||||
Compliance | Safety:EN 62040-1-1(Directive 2006/95/EC); EMC:6200-2(Directive 2004/108/EC) |