X67BC8321.L12 B&R X67 SYSTEM Bus Controller POWERLINK V1/V2 Controlled Node

Brand Name:B&R
Certification:CE
Model Number:X67BC8321.L12
Minimum Order Quantity:1EA
Delivery Time:3-5 working days
Payment Terms:T/T
Contact Now

Add to Cart

Verified Supplier
Location: Xiamen Fujian China
Address: Unit 1602, Top Plaza, No.2 Lujiang Road, Siming District, Xiamen Fujian China
Supplier`s last login times: within 1 hours
Product Details Company Profile
Product Details

X67BC8321.L12 B&R X67 SYSTEM Bus Controller POWERLINK (V1/V2) Controlled Node


MATERIAL NUMBER:

X67BC8321.L12

DESCRIPTION:
  • POWERLINK
  • 16 digital channels, configurable as inputs or outputs
  • M12 connections
  • Integrated hub for efficient cabling
  • I/O configuration and firmware update via the fieldbus
  • Integrated connection to the local expansion via X2X Link for up to 250 additional modules
  • Configurable I/O cycle (starting at 200 ms)

The bus controller makes it possible to connect X2X Link I/O nodes to POWERLINK. It is also possible to operate the X2X Link cycle synchronously 1:1 or synchronous to POWERLINK using a prescaler.

Additional X2X Link I/O nodes (X67 modules or other modules based on X2X Link) can be connected using the integrated X2X Link connection. Mechanically, POWERLINK is connected via an IP67-rated standard D-coded M12 Ethernet connector.

POWERLINK is a standard protocol for Fast Ethernet equipped with hard real-time characteristics. The POWERLINK Standardization Group (EPSG) ensures that the standard remains open and is continually developed:: www.ethernet-powerlink.org.


Short description
Bus controllerPOWERLINK (V1/V2) controlled node
General information
Inputs/Outputs16 digital channels, configurable as inputs or outputs using software, inputs with additional functions
Insulation voltage between channel and bus500 Veff
Nominal voltage24 VDC
B&R ID code
Bus controller0xA90E
Internal I/O module0x1A1D
Sensor/Actuator power supply0.5 A summation current
Status indicatorsI/O function per channel, supply voltage, bus function
Diagnostics
OutputsYes, using LED status indicator and software
I/O power supplyYes, using LED status indicator and software
Connection type
FieldbusM12, D-coded
X2X LinkM12, B-coded
Inputs/Outputs8x M12, A-coded
I/O power supplyM8, 4-pin
Power output15 W X2X Link power supply for I/O modules
Power consumption
Fieldbus4.2 W
Internal I/O2.5 W
X2X Link power supply24.3 W at maximum power output for connected I/O modules
Certifications
CEYes
UKCAYes
ATEXZone 2, II 3G Ex nA IIA T5 Gc
IP67, Ta = 0 - Max. 60°C
TÜV 05 ATEX 7201X
ULcULus E115267
Industrial control equipment
HazLoccCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
EACYes
KCYes
Interfaces
FieldbusPOWERLINK (V1/V2) controlled node
TypeType 2
Variant2x M12 interface (hub), 2x female connector on module
Line lengthMax. 100 m between 2 stations (segment length)
Transfer rate100 Mbit/s
Transfer
Physical layer100BASE-TX
Half-duplexYes
Full-duplexNo
AutonegotiationYes
Auto-MDI/MDIXYes
Hub propagation delay0.96 to 1 µs
Min. cycle time
Fieldbus200 μs
X2X Link200 μs
Synchronization between bus systems possibleYes
I/O power supply
Nominal voltage24 VDC
Voltage range18 to 30 VDC
Integrated protectionReverse polarity protection
Power consumption
Sensor/Actuator power supplyMax. 12 W
Sensor/Actuator power supply
VoltageI/O power supply minus voltage drop for short-circuit protection
Voltage drop for short-circuit protection at 0.5 AMax. 2 VDC
Summation currentMax. 0.5 A
Short-circuit proofYes
Digital inputs
Input characteristics per EN 61131-2Type 1
Input voltage18 to 30 VDC
Input current at 24 VDCTyp. 4 mA
Input circuitSink
Input filter
Hardware≤10 μs (channels 1 to 4) / ≤70 µs (channels 5 to 16)
SoftwareDefault 0 ms, configurable between 0 and 25 ms in 0.2 ms intervals
Input resistanceTyp. 6 kΩ
Additional functions50 kHz event counting, gate measurement
Switching threshold
Low<5 VDC
High>15 VDC
Event counters
Quantity2
Signal formSquare wave pulse
EvaluationEach negative edge, cyclic counter
Input frequencyMax. 50 kHz
Counter 1Input 1
Counter 2Input 3
Counter frequencyMax. 50 kHz
Counter size16-bit
Gate measurement
Quantity1
Signal formSquare wave pulse
EvaluationPositive edge - Negative edge
Counter frequency
Internal48 MHz, 3 MHz, 187.5 kHz
Counter size16-bit
Length of pause between pulses≥100 µs
Pulse length≥20 µs
Supported inputsInput 2 or input 4
Digital outputs
VariantCurrent-sourcing FET
Switching voltageI/O power supply minus residual voltage
Nominal output current0.5 A
Total nominal current8 A
Output circuitSource
Output protectionThermal shutdown in the event of overcurrent or short circuit, integrated protection for switching inductive loads, reverse polarity protection of the output power supply
Diagnostic statusOutput monitoring with 10 ms delay
Leakage current when the output is switched off5 µA
Switching on after overload shutdownApprox. 10 ms (depends on the module temperature)
Residual voltage<0.3 V at 0.5 A nominal current
Peak short-circuit current<12 A
Switching delay
0 → 1<400 µs
1 → 0<400 µs
Switching frequency
Resistive loadMax. 100 Hz
Inductive loadSee section "Switching inductive loads".
Braking voltage when switching off inductive loads50 VDC
Electrical properties
Electrical isolation
Bus isolated from POWERLINK and channel
Channel not isolated from channel
Operating conditions
Mounting orientation
AnyYes
Installation elevation above sea level
0 to 2000 mNo limitation
>2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP67
Ambient conditions
Temperature
Operation-25 to 60°C
Derating-
Storage-40 to 85°C
Transport-40 to 85°C
Mechanical properties
Dimensions
Width53 mm
Height155 mm
Depth42 mm
Weight350 g
Torque for connections
M8Max. 0.4 Nm
M12Max. 0.6 Nm