X20BC0083 B&R X20 PLC SYSTEM Bus Controller POWERLINK V1/V2 Controlled Node

Brand Name:B&R
Certification:COC
Model Number:X20BC0083
Minimum Order Quantity:1EA
Delivery Time:3-5 days
Payment Terms:T/T
Contact Now

Add to Cart

Verified Supplier
Location: Xiamen Fujian China
Address: Unit 1602, Top Plaza, No.2 Lujiang Road, Siming District, Xiamen Fujian China
Supplier`s last login times: within 1 hours
Product Details Company Profile
Product Details

X20BC0083 B&R X20 PLC SYSTEM Bus Controller POWERLINK (V1/V2) Controlled Node

MATERIAL NUMBER:

X20BC0083

DESCRIPTION:
  • POWERLINK
  • I/O configuration and firmware update via the fieldbus
  • Integrated hub for economical wiring

The bus controller makes it possible to connect X2X Link I/O nodes to POWERLINK. It is also possible to operate the X2X Link cycle synchronously 1:1 or synchronous to POWERLINK using a prescaler.

POWERLINK is a standard protocol for Fast Ethernet equipped with hard real-time characteristics. The POWERLINK Standardization Group (EPSG) ensures that the standard remains open and is continually developed

General information
B&R ID code0x1F1E
Status indicatorsModule status, bus function
Diagnostics
Module statusYes, using LED status indicator and software
Bus functionYes, using LED status indicator and software
Power consumption
Bus2 W
Additional power dissipation caused by actuators (resistive) [W]-
Certifications
CEYes
UKCAYes
ATEXZone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
ULcULus E115267
Industrial control equipment
HazLoccCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
DNVTemperature: B(0 - 55°C)
Humidity: B(up to 100%)
Vibration: B(4 g)
EMC: B(bridge and open deck)
LRENV1
KRYes
ABSYes
EACYes
KCYes
Interfaces
FieldbusPOWERLINK (V1/V2) controlled node
TypeType 2
Variant2x shielded RJ45 (hub)
Line lengthMax. 100 m between 2 stations (segment length)
Transfer rate100 Mbit/s
Transfer
Physical layer100BASE-TX
Half-duplexYes
Full-duplexNo
AutonegotiationYes
Auto-MDI/MDIXYes
Hub propagation delay0.96 to 1 µs
Min. cycle time
Fieldbus200 μs
X2X Link200 μs
Synchronization between bus systems possibleYes
Electrical properties
Electrical isolationPOWERLINK isolated from bus and I/O
Operating conditions
Mounting orientation
HorizontalYes
VerticalYes
Installation elevation above sea level
0 to 2000 mNo limitation
>2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation-25 to 60°C
Vertical mounting orientation-25 to 50°C
Derating-
Storage-40 to 85°C
Transport-40 to 85°C
Relative humidity
Operation5 to 95%, non-condensing
Storage5 to 95%, non-condensing
Transport5 to 95%, non-condensing
Mechanical properties
NoteOrder 1x terminal block X20TB12 separately.
Order 1x power supply module X20PS9400 or X20PS9402 separately.
Order 1x bus base X20BB80 separately.
Pitch37.5+0.2mm