X20AO4622 B&R X20 System PLC I/O Module 4 Analog Outputs ±10 V Or 0 To 20 MA / 4 To 20 MA

Brand Name:B&R
Certification:COC
Model Number:X20AO4622
Minimum Order Quantity:1EA
Delivery Time:3-5 DAYS
Payment Terms:T/T
Contact Now

Add to Cart

Verified Supplier
Location: Xiamen Fujian China
Address: Unit 1602, Top Plaza, No.2 Lujiang Road, Siming District, Xiamen Fujian China
Supplier`s last login times: within 1 hours
Product Details Company Profile
Product Details


MATERIAL NUMBER:

X20AO4622

DESCRIPTION:
  • 4 analog outputs
  • Either current or voltage signal possible
  • 13-bit digital converter resolution

X20 analog output module, 4 outputs, 10 V or 0 to 20 mA / 4 to 20 mA, 13-bit converter resolution


General information
B&R ID code0x1BA3
Status indicatorsI/O function per channel, operating state, module status
Diagnostics
Module run/errorYes, using LED status indicator and software
Channel typeYes, using software
Power consumption
Bus0.01 W
Internal I/O1.8 W (Rev. ≥ J0), 2.2 W (Rev. < J0)
Additional power dissipation caused by actuators (resistive) [W]-
Certifications
CEYes
UKCAYes
ATEXZone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
ULcULus E115267
Industrial control equipment
HazLoccCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
DNVTemperature: B(0 - 55°C)
Humidity: B(up to 100%)
Vibration: B(4 g)
EMC: B(bridge and open deck)
LRENV1
KRYes
ABSYes
EACYes
KCYes
Analog outputs
Output±10 V or 0 to 20 mA / 4 to 20 mA, via different terminals
Max. output current10 mA at voltage >5 V
15 mA at voltage <5 V
Digital converter resolution
Voltage±12-bit
Current12-bit
Conversion time300 µs for all outputs
Settling time on output change over entire range500 µs
Switch on/off behaviorInternal enable relay for startup
Max. error
Voltage
Gain0.08%
Offset0.05%
Current
Gain0.09%
Offset0.05%
Output protectionShort-circuit proof
Output format
VoltageINT 0x8001 - 0x7FFF / 1 LSB = 0x0008 = 2.441 mV
CurrentINT 0x0000 - 0x7FFF / 1 LSB = 0x0008 = 4.883 µA
Load per channel
VoltageMax. ±10 mA, load ≥1 kΩ
CurrentLoad max. 600 Ω (Rev. ≥ J0), 500 Ω (Rev. < J0)
Short-circuit proofCurrent limiting ±40 mA
Output filterFirst-order low-pass filter / cutoff frequency 10 kHz
Max. gain drift
Voltage0.015%/°C
Current0.02 %/°C
Max. offset drift
Voltage0.032%/°C
Current0.032%/°C
Error caused by load change
VoltageMax. 0.11%, from 10 MΩ → 1 kΩ, resistive
CurrentMax. 0.5%, from 1 Ω → 600 Ω, resistive
Nonlinearity<0.007%
Insulation voltage between channel and bus500 Veff
Electrical properties
Electrical isolationChannel isolated from bus
Channel not isolated from channel
Operating conditions
Mounting orientation
HorizontalYes
VerticalYes
Installation elevation above sea level
0 to 2000 mNo limitation
>2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation-25 to 60°C (Rev. ≥ J0), 0 to 55°C (Rev. < J0)
Vertical mounting orientation-25 to 50°C (Rev. ≥ J0), 0 to 50°C (Rev. < J0)
DeratingSee section "Derating".
Storage-40 to 85°C
Transport-40 to 85°C
Relative humidity
Operation5 to 95%, non-condensing
Storage5 to 95%, non-condensing
Transport5 to 95%, non-condensing
Mechanical properties
NoteOrder 1x terminal block X20TB12 separately.
Order 1x bus module X20BM11 separately.
Pitch12.5+0.2mm
China X20AO4622 B&R X20 System PLC I/O Module 4 Analog Outputs ±10 V Or 0 To 20 MA / 4 To 20 MA supplier

X20AO4622 B&R X20 System PLC I/O Module 4 Analog Outputs ±10 V Or 0 To 20 MA / 4 To 20 MA