Product Details

0-8KV 0-16KV 0-32KV Cable fault location system


I. Function

Detect main insulation faults of power cables of voltage class up to32kV ; calibrate cable length; accurately

detect cable burial direction and depth.


II. Configuration


Cable fault location systemNameModelQTY
TDRXHGG501C1
Pin pointerXHDD503K1
Cable route tracerXHGX5071
High voltage generatorXHHV532-4C1

III. Main Technical data

1) Windows operating system, touch operation mode, wireless expert online guidance, scientific cable

management, real-time report generation; 10 pulse 10 flashover superposition analysis; built-in operation

instructions, cable data, measured cases.

2) System function: fault distance measurement, fault point location, propagation speed test, cable path

search, buried depth detection, etc.

3) Test methods: low-voltage pulse, flashover method, audio method, acoustic-magnetic synchronization

method, valley method, peak method, electromagnetic induction method, etc.;

4) Display control: Flash tester: 8-inch industrial-grade one-machine control, built-in 12V/7Ah DC power

supply, can work continuously for 8 hours; other is controlled by single-chip microcomputer,

pointer table display;

Test range
test distance30km
detection depth2-10m
Measurement accuracy
rough measurement error±10m (absolute value) or 1%
Sampling frequency100MHz
minimum resolution0.5m (100m/us)
Sampling method:Fully automatic continuous sampling, never miss any single discharge waveform
Low voltage pulseWidth: 0.1uS and 2uS Amplitude: 100Vpp
Output powerpath power: 10W, impact power: 0 ~ 200W
Impact high voltage0~8KV 0~16KV 0~32KV
Short circuit current0 ~ 320mA
Burn through power0 ~ 2450J

IV. Introduction of every part

1. TDR

Introduction

Windows operating system, touch operation mode, wireless expert online guidance, scientific cable

management, real-time report generation; 10 pulse 10 flashover wave superposition analysis; built-in

operation instructions, cable data, measured cases, etc.;

With ranging, speed measurement, cable management and other

Functions

100MHz sampling frequency, minimum resolution 0.5m (100m/us)

Fully automatic continuous sampling, never miss any discharge waveform;

Test method: flashover method, low pressure pulse method, multiple waveform analysis method

Main Specifications:

Pulse amplitude100Vpp
Pulse width0.1uS and 2uS
Measuring distanceSmax: 30km
Smin: 15m
Measurement errorrough measurement absolute error: ±10m
coarse measurement relative error: ±1% (DL/T849.1-2004 specifies no more than ± (1% L + 20) m where: L is the cable length)
Power supply modebuilt-in 12V/7Ah DC power supply, can work continuously for 6 hours or external AC 220V 50Hz power supply

2. PinpointerMC-33


Usage: Work with High voltage generator to determine the exact location of the fault point, that is,

to complete the precise positioning task within the rough measurement range of the cable fault point.

Consist of :

Host machine,acoustic and electromagnetic synchronous sensor, anti-noise headphone and charger

Function and index

1) Acoustic waves and electromagnetic waves generated when the fault point is discharged can be

synchronously received to determine the position of the cable fault point.

2) acoustic and magnetic synchronous pin-point function

Acoustic signal band: center frequency 400Hz,,Band depth:200Hz

Signal:80dB

Pin-point accuracy:0.1m

3) Power supply

Battery: in-built lithium battery, nominal voltage:7.4V, capacity:3000AH

Consumption:300mA,,Continuously work time >9 hours

4) display: 320 X 240 LCD

5) Work condition: temperature: -10℃-40℃, humidity:5-90%RH,Latitude<4500m


Cable route tracer

Usage: Cable path meter is a special instrument for accurately detecting the position and depth of buried

cable in a certain range; path detection is completed by the path signal generator and path signal receiver

(cable fault fixed point meter); The cooperation between the two uses the operation to accurately locate

the cable path within the approximate cable embedding range.

Main composition

Path detection is mainly composed of path signal generator and receiver

Index parameter

Receiver
Work frequency

Low frequency(815hz),

medium frequency(8kHz),

high frequency(33kHz),

radio frequency(83Khz),50Hz


Aerial mode

wave valley(zero mode),

wave peak method(peak mode),

step voltage method and clamp current method (A Frame)

Working modecontinue square wave signal
Signal strengthladder chart,digital range 0-999
Gain controlmanual adjustment, dynamic range:100dB
Detect depthmaximum depth >5m
Maximum detect distance30km
Depth measurementmaximum detect 10m
Accuracy: low frequency±(1-5)%≤2.5m radia frequency:±(5-12)%≤2.5m
path signal generator
Work frequency

low frequency(815hz),

medium frequency(8kHz),

high frequency(33kHz),

radio frequency(83Khz)


Work mode

direct-connection,

coupling method(clamp method),induction method

load5 Ω—3000 Ω
Impedance display5 digits
overheat and overflowautomatic protection
power outputlow, medium and high

4. High voltage generator

The device integrates a DC high-voltage source, a storage capacitor, a discharge ball device, an automatic

discharge device, and a cable fault tester into a cart-type high-end experimental instrument. The device

completely solves the problems of convenience, portability, safety and reliability of the traditional experimental device.

The instrument adopts high-precision, high-stability special high-voltage electronic components and high-frequency

high-voltage technology to make the whole structure simple. In order to preserve the habit of using the transformer

and the operating box to generate DC high voltage, the pulse generator adopts the humanized design operation

mode and integrates the micro reliable circuit design. Safe and reliable, visually intuitive. Really impact the impact

of not bad, but also has automatic timing impact, manual impact and pressure resistance. It is the most humanized

trolley type DC impact high voltage equipment in


It is the ideal product for our power cable fault detection.

the main performance characteristics:

★ High voltage pulse output is uniform and controllable;

★ With a current and voltage double 1.5 level pointer display, intuitive and clear, the impact discharge process is clear at a glance;

★ High-voltage side voltage measurement, accurate in real time;

★ With zero start protection, safe and reliable;

★ Unique high-voltage measurement design, in the stop state, will automatically discharge the internal capacitance of the device;

★ The discharge time can be selected between timing and manual mode;

★ With DC withstand voltage function;

★ Internally installed high-precision test cable fault sampling waveform module;

★ User-friendly design trolley for easy movement.


Main technical index:

Impact high voltage0~8KV 0~16KV 0~32KV optional
High voltage partial pressure

voltage accuracy of 1.5


Built-in capacitor

64/16/4μF


Discharge power2450J
impact timeautomatic impact for about 5 seconds, manual control time
Impact power2KVA
Volume580L × 370W × 1080H
Weightno more than 125KG (4uF)
Working power supplyAC 220V±10% 50Hz±2Hz
Ambient temperature-20~+50°C