Main Features

CT TestPT Test

1) Excitation curve and parameters test

2) Turns ratio test

3) Ratio and phase error test

4) Polarity mark check

5) Winding resistance measurement

6) Secondary burden measurement

7) Error line curve test for protection CT

8) Transient CT parameters test

9) CT nameplate guess

10) Saturation hysteresis loop curve measurement

11) CT Residual Magnetism determination and demagnetization

1) Turns ratio test

2) Ratio error test

3) Phase angle error test

4) Polarity test

5) Secondary burden test

6) Winding resistance test


• Accuracy limit value coefficient(ALF) • Instrument security factor(FS)

Make evaluation for test results according to selected standards

Make word report for test result

Make word reports one time for multi-group test records on the PC

Calculate ratio errors and phase angle errors at rated burden and working burden in one time test

Compare excitation curves with saved excitation curves in the same window


Applications

• CT nameplate guess • CT parameters check in work burden • PT routine test

• CT transient parameters analysis • CT ratio and phase error calibration


Technical Index

Test standardsIEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, C57.13
Power supplyAC220V±10%, 50/60Hz±10%
Voltage/Current output0.1~180V (AC) / 0.001~5A(RMS)
Power output500VA
Maximum knee voltage measurement45KV
Current measurement
Range0~10A (automatically change range in 0.1/0.4/2/10A)
Error<±0.1%+0.01%FS
Voltage measurement
Range0~200V (automatically change range in 1V/10V/70V/200V)
Error< ±0.1%+0.01%FS
Turns ratio measurement & error
Range1~35000
Error1~5000 (error<0.05%) & 5000~35000 (error<0.1%)
Phase measurement
Error & Resolution±2min & 0.01min
Winding resistance measurement
Range0~8kΩ (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm)
Error< 0.2%RDG+0.02%FS
Maximum resolution0.1mΩ
Temperature measure
Range & Error-50~100 Celsius degree & <3 Celsius degree

CT Secondary burden

Range0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)
Error<0.2%RDG+0.02%FS
Maximum resolution0.001ohm

PT Secondary burden

Range0~80kohm (automatically change range in 800ohm/8kohm/80kohm)
Error<0.2%RDG+0.02%FS
Maximum resolution0.1ohm

PT ratio measurement & error

Range1~35000
Error1~10000 (error<0.1%) & 10000~35000 (error<0.2%)
PT ratio error measurement
ErrorTypical error <0.05%, Maximum Error<0.1%
PT phase angle measurement
maximum error< 3min
Others
Memory capacity>1000 groups test results
Working conditiontemperature: -10℃~50℃; moist: ≤90%
Size485mm×356mm×183mm
Weight<15kg