Product Details

AMC16Z-ZA Dual-circuit Data Center Energy Meter

AMC16Z series AC precision power distribution monitoring device is specially designed for data center server power management.The device designed exquisite, can provide A + B 2 incoming and 96 outgoing’s electrical parameters, the input and output switch and the state of lightning protection device with real-time monitoring. All alarm threshold of measurement channels can be set in separate. Over-outgoing triggers system acoustooptic warning immediately. Highly integrated monitoring loop is realized in the volume of traditional instruments.

AMB16Z-ZA can monitor the full power parameters of A+B double-way three-phase AC incoming circuit, 6-way switch state monitoring, 2-way alarm output, 2-way leakage monitoring, 1-way temperature and humidity detection, 1-way RS485 communication, and phase-sequence detection.


Terminals



Technical Parameters


Instrument modelAMC16Z-ZA
Measured parametersVoltage, current, frequency, active power, reactive power, power factor,active power, reactive power
Zero ground voltage, neutral line current, total harmonic content (THD), 2-63 harmonics, current and voltage unbalance degree, current K coefficient (KF), voltage crest coefficient (CF),telephone waveform factor (THFF), peak voltage, voltage and current sequence quantity,environmental temperature and humidity.
Busbar voltageRated220VAC
Measurement±20%
OverloadInstant voltage 2times/second
Current incoming circuitRatedTwice 5A
Range0~6A
OverloadDuration 1.2 times, instantaneous 10 times/second
Temp &humidityTemp range-40℃~+99℃
humidity range20%~90%
Input frequency45~60Hz

Measurement precision

Inlet wireVoltage/current level 0.2, active power/electric energy level 0.5, reactive power/electric energy level 1
Temp±1℃
Humidity±5%
Auxiliary power supplyTake electric signal(≤15W)
EnvironmentTempWorking:-15℃~55℃ Storage:-25℃~70℃
HumidityRelative humidity ≤93%
Altitude≤2500m
Switch output2-way 3A 250VAC/3A 30VDC
Switch input6-way dry contact
CommunicationRS485/Modbus-RTU
Installation methodDIN35mm Guide rail or bottom plate mounting
IP gradeIP20
Class of pollution2
SafetyInsulationAll terminals and the insulation resistance between the conductive pieces not less than 100MΩ
Withstand voltage

A-way voltage and current signal, B-way voltage and current signal, switch output and other ports should meet AC 2KV 1min in pairs, the switch input and other ports should meet ac 0.5KV 1mim, leakage current should be less than 2mA, no breakdown or flashover

Electromagnetic compatibilityAnti static interferenceLevel 4
Electrical fast transient pulse groupLevel 3
Anti-surge interferenceLevel 4
Resistance to radiation of Radio frequency electromagnetic fieldLevel 3