Add to Cart
High Frequency Online UPS 40-120KVA Online UPS 3/3 with colourful touch screen display
CNE series online UPS can meet the highest VFI-SS-111 standard among IEC62040-2 standard; this UPS series can meet all kinds of on-site requirements, adopting high reliability and high intelligent design that have enough ability to exceed the user’s expectations and provide more additional value; the sky-high input power factor and the extremely low input current distortion factor ensured the product green and environment friendly, the higher complete machine efficiency also ensured the its skills. And the system supports more than 6 machines operating in parallel, which achieve the user’s requirement of load increase and expansion upgrade.
10-40KVA
60-300KVA
400-600KVA
High Frequency online UPS features
Support LBS synchronic control;
Support parallel operating and shared battery packs;
All circuit boards are used in three-proofings process;
Configuration EPO Emergency shutdown button;
Adopt digital circulation control technology, which have high
reliability for parallel operation;
The subsystem adopting modular design that is easy for on-site
maintenance;
With super load adaptability, superior overload and short circuit
capability;
Adopt intelligent battery management program to extend the battery
lifespan;
With comprehensive maintenance, support the way of up and down
inlet wire;
With friendly man-machine interface, configured large-screen LCD
touch screen and controllable keyboard that have rich information;
With intelligent system self-diagnosis program, wealthy fault
records, and large capacity historical storage space;
With overlong average fault-free time (>200000h), ultra-low
average maintenance time;
With ultra-wide input voltage and frequency range, which can adapt
to harsh grid environment and adapt to a variety of fuel generator
access as well;
All fans in the system are taken redundant design, with
intelligent speed control function, which greatly improves the
reliability of the system;
With DSP all digital control, which makes the rectifier, inverter,
charging, discharging convert link into all digital control come
true;
With rich optional components: SNMP card, air filter, lightning
protection module, SMS alarm, battery temperature compensation
module., etc.;
Input power factor greater than 0.99, input harmonic current less
than 3%, the whole equipment efficiency greater than 96%, which is
environment protecting and energy efficient;
Three-phase input/three-phase output pure online dual conversion
product, support 380/400/415VAC, 50/60Hz power system that provide
the best power quality and load protection.
Specifications
Model | CNE-3310 | CNE-3315 | CNE-3320 | CNE-3330 | CNE-3340 | CNE-3360 | CNE-3380 | CNE-3390 |
Capacity | 10kVA | 15kVA | 20kVA | 30kVA | 40kVA | 60kVA | 80kVA | 90kVA |
Main Input | ||||||||
Input Voltage | 380/400/415VAC (Line voltage), 50/60Hz | |||||||
Connection mode | Three-phase five-wire system | |||||||
Voltage range | 285~520VAC(Line voltage)full load;216~285VAC(line voltage), load linearly derated from 100% to 75% | |||||||
Frequency range | 40~70Hz | |||||||
Input power factor | ≥0.99 | |||||||
Current distortion factor | <3% | |||||||
Bypass input | ||||||||
Input voltage | 380/400/415VAC | |||||||
Voltage range | Adjustable voltage, default -20%~+15%; upper limit: +10%, +15%, +20%, +25%; lower limit -10%, —15%, -20%, -30%, -40% | |||||||
Frequency range | Adjustable frequency, ±1Hz, ±3Hz, ±5Hz.,etc. | |||||||
Output | ||||||||
Rated output voltage | 380/400/415VAC(Line voltage) | |||||||
Rated output frequency | 50/60Hz | |||||||
Voltage accuracy | ±1% | |||||||
Frequency accuracy | ±0.01% | |||||||
Total harmonic distortion(THD) | ≤1% (Linear load), ≤3% (Non-linear load) | |||||||
Power factor | ≥0.9 | |||||||
Frequency tracking accuracy | 50/60Hz±3Hz (adjustable ±0.5Hz~5Hz) | |||||||
Three phase position accuracy | 120°±0.5° | |||||||
Frequency tracking rate | 0.1Hz/s~5Hz/s (adjustable,default 2Hz/s) | |||||||
Crest factor | ≥3:1 | |||||||
Voltage unbalance rate (100% unbalance load) | ≤3% | |||||||
Overload capacity | 105%,long term operation 110%,convey to bypass after 1hour;125%,convey to bypass after 10mins;150%,convey to bypass after 1minute | |||||||
System | ||||||||
System efficiency | City electricity mode:>96% | |||||||
Battery mode:>96% | ||||||||
ECO mode:≥96% | ||||||||
Battery configuration | 12V,40 batteries (32~44 optional) | |||||||
Display | LCD+ LED+ colorful touch screen | |||||||
EMC | IEC62040-2 | |||||||
IEC61000-4-2(ESD) | ||||||||
IEC61000-4-3(RS) | ||||||||
IEC61000-4-4(EFT) | ||||||||
IEC61000-4-5(Surge) | ||||||||
Insulation resistance | >2M(500VDC) | |||||||
Insulating strength | (Ground input and output)2820Vdc, Leakage current less than 3.5mA, 1 minute non arcing | |||||||
Surge protection | Reach to IEC60664-1 specified IV series installation requirement, that is 1.2/50us+8/20us combination wave less than 6kV/3kA | |||||||
Protection grade | IP20 | |||||||
Communication interface | RS232, RS485, dry contact, SNMP, EPO, generator connector | |||||||
Connection mode | support up and down inlet line | |||||||
Working temperature | 0-40℃ | |||||||
Relative humidity | 0-95%(Non-Condensing) | |||||||
Noise(dB) | <58dB | |||||||
Size(W*D*H)(mm) | 250×660×530 | 250×680×770 | 250×836×770 | 600×980×950 | 600×980×1150 | 600×980×1400 | ||
Weight(Kg) | 30 | 51 | 52 | 61 | 170 | 210 | 232 |
Model | CNE-33100 | CNE-33120 | CNE-33150 | CNE-33200 | CNE-33250 | CNE-33300 | CNE-33400 | CNE-33500 | |||||
Capacity | 100kVA | 120kVA | 150kVA | 200kVA | 250kVA | 300kVA | 400kVA | 500kVA | |||||
Main Input | |||||||||||||
Input Voltage | 380/400/415VAC(Line voltage),50/60Hz | ||||||||||||
Connection mode | Three-phase five-wire system | ||||||||||||
Voltage range | 285~520VAC(Line voltage)full load;216~285VAC(line voltage),load linearly derated from 100% to 75% | ||||||||||||
Frequency range | 40~70Hz | ||||||||||||
Input power factor | ≥0.99 | ||||||||||||
Current distortion factor | <3% | ||||||||||||
Bypass input | |||||||||||||
Input voltage | 380/400/415VAC | ||||||||||||
Voltage range | Adjustable voltage, default -20%~+15%; upper limit: +10%, +15%, +20%, +25%; lower limit -10%, —15%, -20%, -30%, -40% | ||||||||||||
Frequency range | Adjustable frequency, ±1Hz, ±3Hz, ±5Hz., etc. | ||||||||||||
Output | |||||||||||||
Rated output voltage | 380/400/415VAC(Line voltage) | ||||||||||||
Rated output frequency | 50/60Hz | ||||||||||||
Voltage accuracy | ±1% | ||||||||||||
Frequency accuracy | ±0.01% | ||||||||||||
Total harmonic distortion(THD) | ≤1% (Linear load),≤3% (Non-linear load) | ||||||||||||
Power factor | ≥0.9 | ||||||||||||
Frequency tracking accuracy | 50/60Hz±3Hz (adjustable ±0.5Hz~5Hz) | ||||||||||||
Three phase position accuracy | 120°±0.5° | ||||||||||||
Frequency tracking rate | 0.1Hz/s~5Hz/s (adjustable,default 2Hz/s) | ||||||||||||
Crest factor | ≥3:1 | ||||||||||||
Voltage unbalance rate (100% unbalance load) | ≤3% | ||||||||||||
Overload capacity | 105%,long term operation 110%,convey to bypass after 1hour;125%,convey to bypass after 10mins;150%,convey to bypass after 1minute | ||||||||||||
System | |||||||||||||
System efficiency | City electricity mode: >96% | ||||||||||||
Battery mode: >96% | |||||||||||||
ECO mode: ≥99% | |||||||||||||
Battery configuration | 12V, 40 batteries (32~44 optional) | ||||||||||||
Display | LCD+ LED+ colorful touch screen | ||||||||||||
EMC | IEC62040-2 | ||||||||||||
IEC61000-4-2(ESD) | |||||||||||||
IEC61000-4-3(RS) | |||||||||||||
IEC61000-4-4(EFT) | |||||||||||||
IEC61000-4-5(Surge) | |||||||||||||
Insulation resistance | >2M(500VDC) | ||||||||||||
Insulating strength | (Ground input and output)2820Vdc, Leakage current less than 3.5mA, 1 minute non arcing | ||||||||||||
Surge protection | Reach to IEC60664-1 specified IV series installation requirement, that is 1.2/50us+8/20us combination wave less than 6kV/3kA | ||||||||||||
Protection grade | IP20 | ||||||||||||
Communication interface | RS232, RS485, dry contact, SNMP, EPO, generator connector | ||||||||||||
Connection mode | Support up and down inlet line | ||||||||||||
Working temperature | 0-40℃ | ||||||||||||
Relative humidity | 0-95%(Non-Condensing) | ||||||||||||
Noise(dB) | <68dB | ||||||||||||
Size(W*D*H)(mm) | 600×980×1150 | 600×980×1400 | 650×960×1600 | 650×960×2000 | 1300×1100×2000 | ||||||||
Weight(Kg) | 210 | 267 | 306 | 350 | 445 | 490 | 810 | 900 |