Home /

160kw Solar Water Pump Inverter Controller With MPPT 99% PID Controller Solar Vfd

160kw Solar Water Pump Inverter Controller With MPPT 99% PID Controller Solar Vfd

Brand Name:VEIKONG
Certification:CE
Model Number:VFD500-PV
Minimum Order Quantity:1
Delivery Time:depend on the order quantity
Payment Terms:L/C, T/T, Western Union
Contact Now

Add to Cart

Verified Supplier
Location: Shenzhen China
Address: 4F, Building 5, Dongluyang Industrial ,Park, No. 4, Tengfeng 4th Road, Fuyong Phoenix Third, Industrial Zone, Baoan District, Shenzhen China
Supplier`s last login times: within 20 hours
Shipping
lt's easy to get a shipping quote! Just click the button below and complete the short form.
Get Shipping Quote
Product Details Company Profile
Product Details

160kw solar pump inverter with MPPT 99% PID controller solar vfd


Advantage

Half of the energy produced around the world is used to operate pumps. Compared to diesel generator pumps, our solar pump inverter are environmentally friendly, with a long lifetime and low maintenance costs. It is independent from the grid and produces no pollution or noise. Typical applications are irrigation, community water supply, fish farming and agriculture.


All of our drives have many solar-specific and pump control functions, such as built-in maximum power point tracking and dry run detection, as well as sensorless flow calculation.


The maximum power point tracking (MPPT) ensures you to get the best output power possible from your solar panel and it maximizes the performance of your pump along the day while the automatic start and stop with solar radiation can save money and fuel during daylight hours


VEIKONG VFD500-PV solar pumping inverter is specially designed for watering system. A high converting efficiency of 99% and advanced MPPT technology make the solar energy fully used. It converts DC power into AC to drive all kinds of motors. The intelligent design protects the pumps from many abnormal cases, such as over-loading, over-voltage, dry-running, over-heating,low frequency and etc.


Key Features:

1, Support single phase/three phase 220V, and three phase 380V solar water pump inverter, power from 0.75kW to 160KW

2, Simply connect the photovoltaic panel to the inverter, no need to set any parameters.

3, It has protection functions such as overvoltage protection, overcurrent protection, dry runing protection, full water protection.


4, Advanced MPPT algorithm. Ensure solar power tracking efficiency can reach 99.99%

5, Supports optional GPRS module, which can realize remote monitoring function of computer webpage and mobile APP

6, Support PV DC input and grid AC input at same time, which can meet 24 hours of no care work

7, Support LCD keypad, it is easier to monitor system situation.



Electrical Specifications and Power degree

220V

380V

Max input DC voltage

450V

810V

DC voltage range

150~450VDC

300~810VDC

Normal working DC voltage

260V-400V

400V-650V

Recommended input mppt voltage

330V

550V

MPPT efficiency

>99%

Rated output voltage

1/3-phase 220VAC

3-phase 380-480VAC

Output frequency range

50/60Hz

Max efficiency of the machine

99%

Ambient temperature range

-10 °C~50 °C, derating if the temperature is above 40 °C

Cooling method

Air cooling

Protection degree

IP20/IP21

Altitude

Below 1000m; above 1% for every additional 100m.

Standard

CE/ROHS



Accessories:

1. GPRS (support 2g/3g/4g internet)



2. LCD keypad





3. Output Reactor




VFD500-PV solar pump inverter picture:


Connect wire diagram


Techincal Parameters:


1. Wake up and sleep function parameters:


P47.05Light detection thresholdIf the output frequency is lower than this value and exceeds P47.06, it will be reported to Sleep and stop0Hz
P47.06Light detection timeSee P47.05 for explanation.60s
P47.07Light weak wake up timeAfter the sleep fault is reported, if the time when Vdc is higher than the undervoltage point is greater than the set value, the fault state is exited and the operation continues.600s

2. Dry runing protection function parameters:


P24.12Dry run/Unload protection option

0: No offload detection is performed;

1: Enable dry run detection

1
P24.13Dry run/Unload detection level

0.0 to 200.0%

The percentage of motor rated current.

0.0%
P24.14Dry run Unload detection time0.000s~60.000s30.000s
P24.15Unload detection offset frequency

0.00Hz~Fmax

Detection frequency=Fmax-P24.15


5.00Hz
P24.16Reset time of dry run protection0.0~6000.0240.0s
P23.21Dry run detection mode

0000:Coast stop

1000:Fast stop

3000:Continue to run

0000

3. Water full protection function parameters:


P47.18Full water level detection channel

0:ineffective

1:AI1

2:AI2

3:AI3

4:AI4

Note: DI terminal function code 60-full water level detection is same with Analogue detection, and the detection time and recovery time are the same.

0
P47.19Full water level detection value

0.0~100.0%


0.0%
P47.20Full water level detection time

0.0~3000.0s

When DI-60 is valid or meets the analog detection channel greater than P47.19 and maintains P47.20 time, the system reports A.Full and stops.


10.0s
P47.21Full water recovery time

0.0~3000.0s

When the condition described in P47.20 does not meet full water level detection requirement ,it will be returned to normal state after delay

10.0s


China 160kw Solar Water Pump Inverter Controller With MPPT 99% PID Controller Solar Vfd supplier

160kw Solar Water Pump Inverter Controller With MPPT 99% PID Controller Solar Vfd