D.C. Surge Arrester Cubicle
Product introduction:
Normally there are 2 kinds of DC SA for railway system:
1/ 750V, Ur=1.0kV, 8/20μs residual voltage at 20kA: 2.4kV;
2/ 1500V, Ur=2.0kV, 8/20μs residual voltage at 20kA: 4.8kV.
Porcelain surge arrester is of high mechanical strength, longer
creepage distance, excellent electrical insulation performance,
strong dielectric strength, tracking resistance, high- and
low-temperature resistance and sandstorm resistance. The
multi-sealing structure of the housing provides high sealing
performance and long service life.
Shendian takes lead of SA in China, its product is widely used in
State Grid Corporation of China (SGCC) and China Southern Power
Grid (CSG), among them including many extraordinary projects:
(1) 1,000kV UHV Southeast Shanxi Substation of 1,000kV Southeast
Shanxi - Nanyang - Jingmen UHVAC Pilot Demonstration Project,
(2) Extension Works of 1,000kV Nanyang Switching Station of 1,000kV
Southeast Shanxi - Nanyang - Jingmen UHV AC Pilot Demonstration
Project, (3) South Hami Converter Station of ±800kV Hami- Zhengzhou
UHVDC Electricity Transmission Project,
(4) 750kV Qinghai Qaidam Substation and 500kV Baoji - Deyang DC
Electricity Transmission Project, as well as
(5) DC Project of 500kV Hechi Substation of CSG,
(6) DC Project of 500kV Anshun Substation of Guizhou Power Grid
Company and 330kV Sanxing Substation in Xi'an High-tech Zone.
Advantage:
1/ High mechanical strength;
2/ Longer creepage distance;
3/ High dielectric insulation level;
4/ Tolerance to high/low temperature;
5/ Anti-corrosion and anti-aging;
Standard Technical Data:
Below info. only for your reference, all data shall be specified
and determined by technical specification and customer demand.
A: Nominal system voltage ≤55kV
Item | Description | | Offered | Offered | Offered |
1 | Manufacture/ Country of Origin | | Xi'an Shendian/ China |
2 | Model | | Y5WT-42/105 | Y5WT-42/110 | Y5WT-42/120 |
3 | Applicable standard | | IEC 60099-4 | IEC 60099-4 | IEC 60099-4 |
4 | Type | | Outdoor, ZnO, gapless |
5 | Norminal voltage of system | kV | 27.5 | 27.5 | 27.5 |
6 | Earthing system | | Effectively earthed |
7 | Rated frequency | Hz | 50/60 | 50/60 | 50/60 |
8 | Rated voltage of SA | kV | 42 | 42 | 42 |
9 | Maximum continuous operating voltage | kV | 31.5 | 31.5 | 34 |
10 | Power frequency reference voltage | kV | 58 | 60 | 65 |
11 | - at reference current of Note: State peak value or rms. | mA (D.C) | 1 | 1 | 1 |
|
12 | Nominal discharge current | kA | 5 | 5 | 5 |
13 | (a) Lightning impulse | kV | ≤105 | ≤110 | ≤120 |
(b) Steeping impulse | kV | ≤118 | ≤127 | ≤138 |
(c) Switching impulse | kV | ≤89 | ≤94 | ≤98 |
14 | Material employed in series non-linear resistor | | ZnO etc. | ZnO etc. | ZnO etc. |
15 | - Material | | Brown Porcelain | Brown Porcelain | Brown Porcelain |
- Minimum creepage distance | mm/kV | 25/31 | 25/31 | 25/31 |
16 | - HV terminal | | hot zip screw | hot zip screw | hot zip screw |
- earth terminal | | hot zip screw | hot zip screw | hot zip screw |
17 | Diameter of bushing sheds | mm | 232 | 232 | 232 |
18 | Height | mm | 995 | 995 | 995 |
Reference:
1/ Shendian MOA is widely used in China EHV (Extra hight voltage)
projects of State Grid, Southern Power Grid.
2/ Supplied MOA to ABB/Siemens/Schneider more than 20 years, as
well as other capacitor/switchgear manufacturers.
3/ Shendian MOA has been exported to more than 30 counties all over
the world.