Application:

LR2-D series thermal relay can be used in the circuit of 50Hz or 60Hz, rated insulation voltage 660V, rated current 0.1-93A for protecting the phase break when the electric motor is overload.


The relay has different mechanism and temperature compensation & can be pluged in HC-D series AC contactor. It is the most advanced thermal relay in the nineties in the world.


Specifications:

♦ Fundamental parameter of the main circuit

♦ Rated insulation voltage 660V

♦ Rated working current 25,36,93A separately

♦ The regulator seal of rated setting current and setting

♦ Current of the thermal component

♦ Auxiliary circuit

♦ There are one pair of NO and NC contact with electric insulation

♦ Rated frequency 50-60Hz

♦ Use group, rated working voltage, appoint thermal current and rated current


Motion Characteristic: Three-phase Balance Motion Time

NoTimes of the setting currentMotion timeStart conditionAmbient temperature
11.05>2hCold state20±5oC
21.2<2hHeat state(Following the No.1 test)
31.5<4min
47.210A2s< Tp≤10s≤63ACold state
104s< Tp≤10s>63A

Phase-losing Motion Characteristic

NoTimes of the setting currentMotion timeStart conditionAmbienttemperature
Any two phasesAnother phase
11.00.9>2hCold state20±5oC
21.150<2hHeat state(Following the No.1 test)

TypeNumberSetting Range(A)For Contavtor
LR2-D1313010.10~0.16CJX2-09~32
13020.16~0.25CJX2-09~32
13030.25~0.40CJX2-09~32
13040.40~0.63CJX2-09~32
13050.63~1CJX2-09~32
13061~1.6CJX2-09~32
13071.6~2.5CJX2-09~32
13082.5~4CJX2-09~32
13104~6CJX2-09~32
13125.5~8CJX2-12~32
13147~10CJX2-18~32
13169~13CJX2-25~32
132112~18CJX2-25~32
132217~25CJX2-32

Outline & mounting size: