Home /Heat Pump Water Heaters /

Air to Water heat pump efficiency System Saving cost bill

Air to Water heat pump efficiency System Saving cost bill

Brand Name:HISEER
Certification:CE / EN14511
Model Number:AW20-DNNHE
Minimum Order Quantity:2 pieces
Delivery Time:15-20 days after payment
Payment Terms:TT or L/C at sight
Contact Now

Add to Cart

Verified Supplier
Location: Foshan Guangdong China
Address: Head Office:Room 1006, Building A, Star Plaza, No. B270, East Lecong Avenue, Lecong Town, Shunde District, Foshan City, Guangdong Province, China.
Supplier`s last login times: within 38 hours
Shipping
lt's easy to get a shipping quote! Just click the button below and complete the short form.
Get Shipping Quote
Product Details Company Profile
Product Details

Air to Water heat pump efficiency System Saving cost bill

AW20-DNNHE, HISEER air source heat pump utilizes ambient air as the source of energy to heat or cool your house, and offer domestic hot water.
AW20-DNNHE include automatic started emersion heater by the outside temperature. Characterized by its high quality, competitive price and high efficiency and ease installation,

HISEER AW20-DNNHE adopts the following world famous parts:

  • SWEP or GEA plate type heat exchanger
  • Siemens controller
  • Hitachi scroll compressor
  • Emersion thermal expansion valve
  • Emersion dry filter
  • Schneider A/C contactor
  • Honeywell R410a refrigeration

As a heat source, air is the most accessible. It is readily available and practically unlimited. Heat pumps taking heat from the air are called “air-water“. The heat contained in the air is used directly. The heat pump evaporator is placed outside the building and the heat contained in the air warms up the refrigerant, which evaporates and turns to gas.


Air source heat pumps use the refrigeration process to transfer low grade energy from the air outside into high grade energy used for heating and domestic hot water. Even at temperatures as low as -20˚C, an air source heat pump can supply significantly more energy than it uses – and with no local C02 emissions, it helps reduce impact on the environment.


Heat pumps are measured by their coefficient of performance (COP). The COP for air source heat pumps is very similar to that for ground source heat pumps at approximately 2-4. With a COP for instance of 4, 4 units of heat are produced for every 1 unit of electricity consumed. (The three free units of heating were extracted from the outside air). Even with ambient air temperatures of -10 to -15 degrees Celsius, an air source heat pump can extract useful heat (i.e. > 1 unit of heat generated per unit of electricity consumed).


Advantages:

  • Utilization all the year round for heating, cooling as well as hot water
  • Low investment costs with high quality
  • Easy installation
  • Silent operation
  • Reducing your carbon emission
  • Enjoying your green life by installing HISEER heat pumps
  • Reducing your heating and cooling bill with high efficiency HISEER heat pumps

AW20-DNNHE technical data

AIR TO WATER HEAT PUMP

AW20-DNNHE

Heat output/Power consumption at 7/35℃

kW

21.7/5.7

Heat output/Power consumption at 7/45℃

kW

21.4/6.8

Heat output/Power consumption at 7/55℃

kW

20.8/8.4

Heat output/Power consumption at 2/35℃

kW

18.9/5.7

Heat output/Power consumption at 2/45℃

kW

18.5/6.8

Heat output/Power consumption at -7/35℃

kW

14.3/5.8

Heat output/Power consumption at -7/45℃

kW

14.2/6.9

Starting current

A

74

Power

 

380-415V/3PH/50Hz

Compressor

 

HITACHI scroll

Condenser

 

Brazed plate heat exchanger

Nominal flow heating medium

l/s

1.03

Internal pressure drop at nominal flow

kPa

24

Air flow

m3/h

6000

Nominal output fan

W

440

Max outgoing heating medium temperature

55℃

Dimensions(HxWxD)

mm

1050x1300x690

Pipe connector

 

DN40

Weight

kg

270

The above data is tested by EN14511

China Air to Water heat pump efficiency System Saving cost bill supplier

Air to Water heat pump efficiency System Saving cost bill

Inquiry Cart 0