Double-Conversion Three Phase Tower UPS 15KVA Overcurrent Protect Adjustable Battery Numbers Online UPS

Brand Name:Visench
Model Number:Pro-15K
Minimum Order Quantity:1
Delivery Time:30days
Place of Origin:China
Supply Ability:10000pcs/month
Contact Now

Add to Cart

Verified Supplier
Location: Shenzhen China
Address: Room 1218, Building 3, Futong Haizhi Science Park, Xialilang Community, Nanwan Street, Longgang District, Shenzhen
Supplier`s last login times: within 46 hours
Product Details Company Profile
Product Details

XT Series (three-three phase)

PRODUCT SPECIFICATION ADVANCED POINTS

1. Large input voltage range: full load: 207Vac-475Vac; no-load:210Vac-475Vac

2. Large input frequency range: The UPS can work in mains INV mode if the input ranges from 40 to 70Hz.

3. High output accuracy: ±1% output voltage error.


PRODUCT FEATURES

1. High-frequency online three-in and three-out UPS, the output can be connected to unbalanced load, and the input three-phase always keeps the load balanced.

2. Fully digital control,more stable performance.

3. Energy-saved and environmental protection, efficiency is up to 93%

4. Support N+X parallel redundancy

5. The most optimized tower structure design has the smallest volume compared to similar products on the market

6. A single set of battery supplies power to the system, reducing the number of batteries and save cost.

7. 10-20K standard machine integrated design with battery built-in, easy to install and use.

8. Visualized LCD display interface, clear and intuitive display of three-phase working information.

9. Intelligent mobile monitoring cards are supported to monitor UPS data in real time through mobile apps.


PARAMETER XT33 10-40KVA
ModelXT33 10KVAXT33 10KSXT33 20KVAXT33 20KSXT33 30KSXT33 40KS
Rated Power 10kVA/9kW20kVA/18kW30kVA/27kW40kVA/36kW
InputVoltage Range207-475Vac 3P4W+G
Working Frequency Range40-70Hz (settable)
Input Power Factor≥0.99
OutputRated Voltage and Accuracy380Vac(1±1%) 3P4W+G
Output Frequency46-54Hz synchronize with mains power; 50Hz (Mains power between 40-46Hz and 54-60Hz ); 50Hz(Battery)
Rated Current15A30A45A61A
Output Power Factor0.9
Output Harmonic Wave≤3% (Full R load)
Crest Factor  3:1  
Output Overload105%±5%<Load≤125%±5%: Convert to bypass output and alarm after 1min;
125%±5%<Load≤150%±5%: Convert to bypass output and alarm after 30s;
Load>150%±5%: Convert to bypass output and alarm after 300ms.
Conversion time between Mains Power and Battery0ms
Efficiency>92%>91%
BatteryRated Voltage192Vdc±192Vdc
Quantity1632
Charging Current1A5.5A1A7.5A5.5A
Dimension (LxWxH) mm560x260x717533x260x501710x260x717710x260x717
Weight72kg26kg98kg57.5kg58.5kg62kg
Working Temperature0℃-40℃
Working Humidity20%-95% (non-condensing)
Noise≤60dB

China Double-Conversion Three Phase Tower UPS 15KVA Overcurrent Protect Adjustable Battery Numbers Online UPS supplier

Double-Conversion Three Phase Tower UPS 15KVA Overcurrent Protect Adjustable Battery Numbers Online UPS

Inquiry Cart 0