Add to Cart
The device is used in conductive liquids (as of 10 μs/cm) for determining level limits.
Depending on the number of measuring points (up to 5 rods or ropes), measuring tasks such as overspill protection, dry running protection, two- point control of pumps or multiple point detection can be implemented for an existing process connection.
Dimensions
Type Code
L | K | L | – | P | 1 | – | (1) | (2) | (3) | – | (4) | (5) | (6) | – | (7) | . | L |
LKL-P | Device |
LKL-P | Conductive limit switch |
1 | Design |
1 | Device with rod probe |
(1) | Process connection |
G5 | Thread G1-1/2, DIN/ISO 228/1, plastic PPS |
N5 | Thread NPT1-1/2, ANSI, plastic PPS |
(2) | Quantity and rod type |
2 | 2 rods, stainless steel 1.4404/316L |
3 | 3 rods, stainless steel 1.4404/316L |
5 | 5 rods, stainless steel 1.4404/316L |
(3) | Probe length |
A | Specified length L in mm, 100 mm to 4000 mm |
B | Specified length L in inch, 3.9 inch to 157.5 inch |
C | 1000 mm |
D | 2000 mm |
(4) | Housing |
P1 | Plastic housing, IP66, M20x1,5 |
P2 | Plastic housing, IP66, NPT1/2 |
P3 | Plastic housing, IP66, G1/2 |
(5) | Electrical output |
E5 | FEW52, PNP, 10.8 V to 45 V DC |
N1 | FEW58, NAMUR |
NA | Separate instrumentation (without electronic insert) |
WA | FEW54, relay, 20 V to 253 V AC |
XX | Electronics retrofittable |
(6) | Additional equipment |
N | without additional equipment |
Y | Special version |
(7) | Approval |
NA | Version for non-explosion-hazardous area |
EB | ATEX II 2G Ex ia/ib IIB/IIC T6...T5 Gb |
WH | WHG overfill protection |