P+F Switch Amplifier KFD2-SR2-Ex2.W with B2 Housing Type

Brand Name:P+F
Certification:CE
Model Number:KFD2-SR2-Ex2.W
Minimum Order Quantity:1pc
Delivery Time:on request
Payment Terms:T/T
Contact Now

Add to Cart

Verified Supplier
Location: Hong kong China
Address: Unit 1406B 14/F,The Belgian Bank Building, Nos. 721-725 Nathan Road, Mongkok, Kowloon,Hong kong.
Supplier`s last login times: within 39 hours
Product Details Company Profile
Product Details

P+F Switch Amplifier KFD2-SR2-Ex2.W

This isolated barrier is used for intrinsic safety applications.

The device transfers digital signals from NAMUR sensors or dry contacts from the hazardous area to the non-hazardous area.
The proximity sensor or the mechanical contact controls the control side load for a relay contact output. The device output changes the state when
the input signal changes the state.
Via switches the mode of operation can be reversed and the line fault detection can be switched off.
During a fault condition, the relay reverts to its de-energized state and the LEDs indicate the fault according to NAMUR NE 44.
If the device is operated via Power Rail, additionally a collective error message is available.

General specifications

Signal type

Digital Input

Functional safety related parameters

Safety Integrity Level (SIL)

SIL 2

Systematic capability (SC)

SC 3

Supply

Connection

Power Rail or terminals 14+, 15-

Rated voltage

19 ... 30 V DC

Ripple

≤ 10 %

Rated current

≤ 50 mA

Power dissipation

≤ 1 W

Power consumption

≤ 1 W

Input

Connection side

field side

Connection

terminals 1+, 2+, 3-; 4+, 5+, 6-

Rated values

acc. to EN 60947-5-6 (NAMUR)

Open circuit voltage/short-circuit current

approx. 8 V DC / approx. 8 mA

Switching point/switching hysteresis

1.2 ... 2.1 mA / approx. 0.2 mA

Line fault detection

breakage I ≤ 0.1 mA , short-circuit I > 6 mA

Pulse/Pause ratio

min. 20 ms / min. 20 ms

Output

Connection side

control side

Connection

output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12

Output I, II

signal, relay

Contact loading

250 V AC/2 A/cos φ > 0.75; 126.5 V AC/4 A/cos φ > 0.75; 40 V DC/2 A resistive load

Minimum switch current

2 mA / 24 V DC

Energized/De-energized delay

approx. 20 ms / approx. 20 ms

Mechanical life

107 switching cycles

Collective error message

Power Rail

Transfer characteristics

Switching frequency

≤ 10 Hz

Galvanic isolation

Input/Output

reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Input/power supply

reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Output/power supply

reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Output/Output

reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Indicators/settings

Display elements

LEDs

Control elements

DIP switch

Configuration

via DIP switches

Labeling

space for labeling at the front

Directive conformity

Electromagnetic compatibility



Directive 2014/30/EU

EN 61326-1:2013 (industrial locations)

Low voltage



Directive 2014/35/EU

EN 61010-1:2010+A1:2019+A1:2019/AC:2019

Conformity

Electromagnetic compatibility

NE 21:2017 , EN 61326-3-1:2017 , EN IEC 61326-3-2:2018

Degree of protection

IEC 60529:1989+A1:1999+A2:2013

Functional safety

IEC/EN 61508:2010

Input

EN 60947-5-6:2000

Ambient conditions

Ambient temperature

-40 ... 70 °C (-40 ... 158 °F)

Mechanical specifications

Degree of protection

IP20

Connection

screw terminals

Mass

approx. 150 g

Dimensions

20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2


Height

119 mm


Width

20 mm


Depth

115 mm

Mounting

on 35 mm DIN mounting rail acc. to EN 60715:2001

Data for application in connection with hazardous areas

EU-type examination certificate

PTB 00 ATEX 2080


Marking

II (1)G [Ex ia Ga] IIC
II (1)D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I


Input

Ex ia


Voltage

10.5 V


Current

13 mA


Power

34 mW (linear characteristic)

Supply



Maximum safe voltage

253 V AC / 125 V DC (Attention! Um is no rated voltage.)

Output



Maximum safe voltage

253 V AC (Attention! The rated voltage can be lower.)

Fault indication output



Maximum safe voltage

40 V DC (Attention! Um is no rated voltage.)

Certificate

PF 08 CERT 0803


Marking

II (3)G [Ex ic Gc] IIC

Input

Ex ic


Voltage

10.5 V


Current

13 mA


Power

34 mW (linear characteristic)

Certificate

TÜV 99 ATEX 1493 X


Marking

II 3G Ex ec nC IIC T4 Gc

Galvanic isolation



Input/Output

safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V


Input/power supply

safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V

Directive conformity



Directive 2014/34/EU

EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN IEC 60079-15:2019

International approvals

FM approval



FM certificate

FM19US0207X


Control drawing

116-0035

UL approval

E106378


Control drawing

116-0473 (cULus)


Contact loading

250 V AC/2 A/cos φ > 0.75; 126.5 V AC/4 A/cos φ > 0.75; 30 V DC/2 A resistive load

IECEx approval



IECEx certificate

IECEx PTB 11.0034 , IECEx TUN 19.0013X


IECEx marking

[Ex ia Ga] IIC
[Ex ia Da] IIIC
[Ex ia Ma] I
Ex ec nC IIC T4 Gc


China P+F Switch Amplifier KFD2-SR2-Ex2.W with B2 Housing Type supplier

P+F Switch Amplifier KFD2-SR2-Ex2.W with B2 Housing Type

Inquiry Cart 0