IEC 60529:2001 P+F Sensors Switch Amplifier KFA6-SR2-Ex2.W

Brand Name:P+F
Certification:PTB 00 ATEX 2081
Model Number:KFA6-SR2-Ex2.W
Minimum Order Quantity:1 piece
Delivery Time:on request
Payment Terms:T/T
Contact Now

Add to Cart

Verified Supplier
Location: Hong kong China
Address: Unit 1406B 14/F,The Belgian Bank Building, Nos. 721-725 Nathan Road, Mongkok, Kowloon,Hong kong.
Supplier`s last login times: within 39 hours
Product Details Company Profile
Product Details

Switch Amplifier KFA6-SR2-Ex2.W


2-channel isolated barrier, 230 V AC supply, Dry contact or NAMUR inputs, Relay contact output, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 207 ... 253 V AC, 45 ... 65 Hz, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x relay (change-over contact), Reversible mode of operation


Technical Data


General specifications

Signal type

Digital Input

Functional safety related parameters

Safety Integrity Level (SIL)

SIL 2

Supply

Connection

terminals 14, 15

Rated voltage

207 ... 253 V AC, 45 ... 65 Hz

Power dissipation

1.2 W

Power consumption

max. 1.3 W

Input

Connection side

field side

Connection

terminals 1+, 2+, 3-; 4+, 5+, 6-

Rated values

acc. to EN 60947-5-6 (NAMUR)

Open circuit voltage/short-circuit current

approx. 8 V DC / approx. 8 mA

Switching point/switching hysteresis

1.2 ... 2.1 mA / approx. 0.2 mA

Line fault detection

breakage I ≤ 0.1 mA , short-circuit I > 6 mA

Pulse/Pause ratio

min. 20 ms / min. 20 ms

Output

Connection side

control side

Connection

output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12

Output I, II

signal ; relay

Contact loading

253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load

Energized/De-energized delay

approx. 20 ms / approx. 20 ms

Mechanical life

107 switching cycles

Transfer characteristics

Switching frequency

≤ 10 Hz

Galvanic isolation

Input/Output

reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Input/power supply

reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Output/power supply

reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Output/Output

reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Indicators/settings

Display elements

LEDs

Labeling

space for labeling at the front

Directive conformity

Electromagnetic compatibility



Directive 2014/30/EU

EN 61326-1:2013 (industrial locations)

Low voltage



Directive 2014/35/EU

EN 61010-1:2010

Conformity

Electromagnetic compatibility

NE 21:2006

Degree of protection

IEC 60529:2001

Input

EN 60947-5-6:2000

Ambient conditions

Ambient temperature

-20 ... 60 °C (-4 ... 140 °F)

Mechanical specifications

Degree of protection

IP20

Connection

screw terminals

Mass

approx. 150 g

Dimensions

20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2


Height

119 mm


Width

20 mm


Depth

115 mm

Mounting

on 35 mm DIN mounting rail acc. to EN 60715:2001

Data for application in connection with hazardous areas

EU-type examination certificate

PTB 00 ATEX 2081


Marking

II (1)G [Ex ia Ga] IIC
II (1)D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I


Input

Ex ia


Voltage

10.6 V


Current

19.1 mA


Power

51 mW (linear characteristic)

Supply



Maximum safe voltage

253 V AC (Attention! Um is no rated voltage.)

Output



Contact loading

253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load


Maximum safe voltage

253 V AC (Attention! The rated voltage can be lower.)

Galvanic isolation



Input/input

not available


Input/Output

safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V


Input/power supply

safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V

Directive conformity



Directive 2014/34/EU

EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012

International approvals

FM approval



Control drawing

116-0035

UL approval



Control drawing

116-0145

CSA approval



Control drawing

116-0047

IECEx approval



IECEx certificate

IECEx PTB 11.0031


IECEx marking

[Ex ia Ga] IIC
[Ex ia Da] IIIC
[Ex ia Ma] I


Related Models:


KFU8-UFT

KFD0-CS-Ex1.51P

K-HM26-2M-261533

KFD0-CS-Ex2.50P

NBB15-U1-E2

KFD0-CS-Ex2.51P

NBB1,5-5GM25-E2

KFD0-RO-Ex2

NBB1,5-5GM25-E2-V3

KFD0-SCS-Ex1.55

NBB1,5-F79-E0

KFD0-SD2-Ex2.1045

NBB1,5-F79-E2

KFD0-SD2-Ex2.1245

NBB15-U1-Z2

KFD0-TR-Ex1

NBB5-18GM50-E2-V1

KFD0-CC-1

NBB15-30GM30-E2-V1

KFD0-HMS-16

NBB15-30GM50-A2-V1

KFD0-RSH-1.4S.PS2

NBB15-30GM50-E2

KFD0-SD2-EX1.10100

NBB15-30GM50-E2-M

KFD0-SD2-EX1.1045

NBB15-30GM50-E2-V1

KFD2-UT2-1

NBB15-30GM50-E2-V1-M

KFD2-CD-1.32

NBB8-18GM30-E2

KFD2-CD-EX1.32

NBB8-18GM30-E2-V1

KFD2-HMM-16

NBB8-18GM60-A2-V1

KFD2-SH-EX1.T

NJ4-12GK-SN

KFD2-UT2-1

NJ5-18GK-N

KFD2-VR4-EX1.26

NJ5-18GK-N-150

KFU8-UFC-1.D

NJ5-18GM-N

V15-G-2M

NJ8-18GK-N

Z 787

RD0-FB-EX4

Z787.H

RD0-TI-Ex8.FF.*

HIC2031

Z787.F

Z787.H.F




China IEC 60529:2001 P+F Sensors Switch Amplifier KFA6-SR2-Ex2.W supplier

IEC 60529:2001 P+F Sensors Switch Amplifier KFA6-SR2-Ex2.W

Inquiry Cart 0