1-channel isolated barrier, 230 V AC supply, Dry contact or NAMUR inputs, Input frequency 1 mHz ... 5 kHz, 2 relay contact outputs, Start-up override, Configurable by keypad, Line fault detection (LFD), Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 40 mm, Number of channels: 1-channel, Trip relay, Start-up override, Rotation speed monitoring, Safety Integrity Level (SIL): SIL 2, Rated voltage: 230 V AC ± 10 %, Field device: NAMUR sensor, Field device [2]: volt-free contact
Technical Data
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | terminals 23, 24 | |
Rated voltage | 230 V AC ± 10 % | |
Rated current | 18 mA | |
Power dissipation/power consumption | ≤ 2 VA / 2 VA | |
Input | ||
Connection side | field side | |
Connection | Input I: intrinsically safe: terminals 1+, 3- | |
Input I | acc. to EN 60947-5-6 (NAMUR) | |
Pulse duration | > 50 µs | |
Input frequency | 0.001 ... 5000 Hz | |
Line fault detection | breakage I ≤ 0.15 mA; short-circuit I > 6.5 mA | |
Input II | startup override: 1 ... 1000 s, adjustable in steps of 1 s | |
Active/Passive | I > 4 mA (for min. 100 ms)/ I < 1 mA | |
Open circuit voltage/short-circuit current | 18 V / 5 mA | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 10, 11, 12 | |
Output I, II | signal, relay | |
Contact loading | 253 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A | |
Mechanical life | 5 x 107 switching cycles | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Transfer characteristics | ||
Input I | ||
Measurement range | 0.001 ... 5000 Hz | |
Resolution | 0.1 % of measured value , ≥ 0.001 Hz | |
Accuracy | 0.1 % of measured value , > 0.001 Hz | |
Measuring time | < 100 ms | |
Influence of ambient temperature | 0.003 %/K (30 ppm) | |
Output I, II | ||
Response delay | ≤ 200 ms | |
Galvanic isolation | ||
Input I/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Output I, II against eachother | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Output I, II/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Start-up override/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Indicators/settings | ||
Display elements | LEDs , display | |
Control elements | Control panel | |
Configuration | via operating buttons | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | 300 g | |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2 | |
Height | 119 mm | |
Width | 40 mm | |
Depth | 115 mm | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | TÜV 99 ATEX 1408 | |
Marking | II (1)G [Ex ia Ga] IIC | |
Supply | ||
Maximum safe voltage | 253 V AC (Attention! Um is no rated voltage.) | |
Input I | terminals 1+, 3-: Ex ia | |
Voltage Uo | 10.1 V | |
Current Io | 13.5 mA | |
Power Po | 34 mW (linear characteristic) | |
Input II | terminals 13+, 14- non-intrinsically safe | |
Maximum safe voltage Um | 40 V (Attention! The rated voltage can be lower.) | |
Output I, II | terminals 10, 11, 12; 16, 17, 18 non-intrinsically safe | |
Maximum safe voltage | 253 V (Attention! The rated voltage can be lower.) | |
Contact loading | 253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load | |
Certificate | TÜV 02 ATEX 1885 X | |
Marking | II 3G Ex nA nC IIC T4 Gc | |
Output I, II | ||
Contact loading | 50 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load | |
Galvanic isolation | ||
Input I/other circuits | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 16-538FM-12 | |
UL approval | E223772 | |
IECEx approval | ||
IECEx certificate | IECEx TUN 03.0000 | |
IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I |
Related Models:
KFU8-UFT | KFD0-CS-Ex1.51P | NBB8-18GM50-A2-V1 |
K-HM26-2M-261533 | KFD0-CS-Ex2.50P | NBB8-18GM50-E0 |
NBB15-U1-E2 | KFD0-CS-Ex2.51P | NBB8-18GM50-E0-V1 |
NBB1,5-5GM25-E2 | KFD0-RO-Ex2 | NBB8-18GM50-E2 |
NBB1,5-5GM25-E2-V3 | KFD0-SCS-Ex1.55 | NBB8-18GM50-E2-V1 |
NBB1,5-F79-E0 | KFD0-SD2-Ex2.1045 | NBB8-18GM50-E2-V1-M |
NBB1,5-F79-E2 | KFD0-SD2-Ex2.1245 | NBB8-18GM60-A2-V1 |
NBB15-U1-Z2 | KFD0-TR-Ex1 | NBB8-18GM60-US |
NBB5-18GM50-E2-V1 | KFD0-CC-1 | NBN3-8GM40-E2-V3 |
NBB15-30GM30-E2-V1 | KFD0-HMS-16 | NBN3-F25F-E8-V1 |
NBB15-30GM50-A2-V1 | KFD0-RSH-1.4S.PS2 | NBN40-U1K-N0 |
NBB15-30GM50-E2 | KFD0-SD2-EX1.10100 | NBN40-U4LK-N0 |
NBB15-30GM50-E2-M | KFD0-SD2-EX1.1045 | NBVB15-U1.Z2 |
NBB15-30GM50-E2-V1 | KFD2-UT2-1 | NCB5-18GM40-NO |
NBB15-30GM50-E2-V1-M | KFD2-CD-1.32 | NJ10-30GM-N-5M |
NBB8-18GM30-E2 | KFD2-CD-EX1.32 | NJ15-30GK-N |
NBB8-18GM30-E2-V1 | KFD2-HMM-16 | NJ2-12GK-SN |
NBB8-18GM60-A2-V1 | KFD2-SH-EX1.T | NJ2-12GM-N |
NJ4-12GK-SN | KFD2-UT2-1 | RD0-FB-EX4.COM |
NJ5-18GK-N | KFD2-VR4-EX1.26 | SC3,5-G-N0 |
NJ5-18GK-N-150 | KFU8-UFC-1.D | SC3,5-G-N0-5M |
NJ5-18GM-N | V15-G-2M | SC3,5-G-N0-6M |
NJ8-18GK-N | Z 787 | SJ3,5-N |
RD0-FB-EX4 | Z787.H | SJ3,5-S1N |
RD0-TI-Ex8.FF.* | HIC2031 | UPR-03 |
Z787.F | Z787.H.F | SJ3,5-N-BU |