Material number:

X20CM0985

Description:

  • Energy measurement for 120 to 480 VAC

  • Simultaneous measurement of 2 AC mains networks plus 2 additional voltages

  • For multifunctional measurement tasks

  • Intelligent mains synchronization unit

The module has a compact size and combines a power measurement module that has special features with a synchronization unit that is able to meet all demands.

The measurement unit's 3 current inputs are suitable for both X: 1 A and X: 5 A current transformers. Overcurrent resistance and the high resolution of the measurement unit round off its features. For the voltage inputs, the value range can be configured between 480 VAC and 120 VAC.

The area of use includes 4-wire AC networks with a phase voltage up to 480 VAC and 3-wire systems, whereas L2 can be grounded (V-connection). The module can also handle Aron measuring circuits.

The resulting measured values include the pure phase current; line-to-line voltage or phase voltage; the effective, reactive and apparent power parts; the mains frequency; the power factor and much more. In addition, peak values and energy meters are stored on the module in nonvolatile memory. Depending on the configuration, it is also possible to use a digital output as a pulse encoder for an external energy meter.

The synchronization unit doesn't just take the phasing and phase voltage into consideration; integrated intelligence also monitors the rate of change and other parameters, allowing them to influence when the synchronization output is switched. It is also possible to monitor a generator using a large number of additional conditions. A total of 4 voltage inputs provide substantial overall flexibility.

Monitoring functions expand the features of the module. Dependent overcurrent monitoring is included, which utilizes the thermal capacity of the motor/generator to allow short overloads while still providing full protection. The dependent, delayed imbalanced load monitoring used to protect three-phase generator and three-phase networks from imbalanced load can be adapted to the characteristics of different generator types using parameters while taking their special thermal time constants into account.


Product Information




Short description

I/O module

X20 energy measurement and synchronization module

General information

B&R ID code

0x2433

Status indicators

Channel status, operating state, module status

Diagnostics


Module run/error

Yes, using LED status indicator and software

Analog inputs

Yes, using LED status indicator (measurement range of analog inputs)

Digital outputs

Yes, using LED status indicator and software

Overvoltage category

ll

Power consumption


Bus

1.4 W

Internal I/O

4 W

Additional power dissipation caused by actuators (resistive) [W]

-

Certifications


CE

Yes

UKCA

Yes

ATEX

Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X

UL

cULus E115267
Industrial control equipment

HazLoc

cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5

KC

Yes

Digital outputs

Quantity

5

Variant

Current-sourcing FET

Nominal voltage

24 VDC

Switching voltage

24 VDC -15% / +20%

Nominal output current

0.1 A

Total nominal current

0.5 A

Connection type

1-wire connections

Output circuit

Source

Output protection

Thermal shutdown in the event of overcurrent or short circuit

Diagnostic status

Output monitoring with 10 ms delay

Leakage current when the output is switched off

5 μA

Residual voltage

<0.3 V at 0.1 A nominal current

Peak short-circuit current

<2 A

Switch-on in the event of overload shutdown or short-circuit shutdown

Approx. 10 ms, depends on the module temperature

Switching delay


0 → 1

<300 μs

1 → 0

<300 μs

Switching frequency


Resistive load

Max. 100 Hz

Insulation voltage between channel and bus

500 Veff

Relay outputs

Quantity

1

Variant

Relay / Changeover contact

Nominal voltage

30 VDC / 240 VAC

Rated frequency

DC / 45 to 63 Hz

Switching capacity


Min.

10 mA / 5 VDC

Max.

30 W / 240 VAC

Nominal output current

1 A at 30 VDC / 1 A at 240 VAC

Actuator power supply

External

Switching voltage

Max. 60 VDC / 250 VAC

Switching delay


0 → 1

≤10 ms

1 → 0

≤10 ms

Service life


Mechanical

Min. 10 x 106ops.

Electrical

Min. 60 x 103ops. (NC) at 1 A
Min. 30 x 103ops. (NO) at 1 A

Contact resistance

Max. 100 mΩ

Protective circuit


Internal

None

External

None

DC

Inverse diode, RC combination or VDR

AC

RC combination or VDR

Insulation voltage


Channel - Channel

1000 VAC / 1 min

Channel - Bus

4000 VAC / 1 min

Analog input voltage

Channels

8

Input

120 VAC / 480 VAC

Input type

Single-ended

Digital converter resolution

±15-bit

Conversion time


50 Hz

20 ms

60 Hz

16.67 ms

Permissible input signal

Max. 132 VAC / 528 VAC

Output format


±120 VAC

1 LSB = 0x0001 = 5.707 mV

±480 VAC

1 LSB = 0x0001 = 22.787 mV

Output of digital value during overload


Overshoot

0x7FFF

Undershoot

0x8001

Conversion method

SAR

Input filter


Cutoff frequency

10 kHz

Slope

60 dB

Maximum gain drift

0.02% per °C

Maximum offset drift

0.003% per °C

Crosstalk between channels

-70 dB

Nonlinearity

≤0.5% at 45 to 65 Hz

Protection against electric shock

Protective impedance per EN 61131-2

Test voltage between channel and bus (type test)

3700 Veff

Output format

INT

Input impedance in signal range

Approx. 3 MΩ

Max. error at 25°C


Gain

0.09%

Offset

0.03%

Input protection

Overvoltage protection

Analog input current

Channels

3

Input

1 A / 5 A AC

Input type

Isolated current transformer according to the compensation principle with a magnetic sensor, for connecting an external transformer

Digital converter resolution

±15-bit

Conversion time


50 Hz

20 ms

60 Hz

16.67 ms

Permissible input signal

Max. 1.5 A / 7.7 A

Output format


±1 A

1 LSB = 0x0001 = 189.903 μA

±5 A

1 LSB = 0x0001 = 949.513 μA

Output of digital value during overload


Overshoot

0x7FFF

Undershoot

0x8001

Conversion method

SAR

Input filter


Cutoff frequency

10 kHz

Slope

60 dB

Maximum gain drift

0.07% per °C

Maximum offset drift

0.003% per °C

Crosstalk between channels

-70 dB

Nonlinearity

≤0.5% at 45 to 65 Hz

Insulation voltage between channel and bus

500 Veff

Output format

INT

Max. error at 25°C


Gain

0.2%

Offset

0.05%

Thermal overcurrent

15 x INom for 0.2 s

Monitored overcurrent

4 x INom

Input impedance


Measurement range 1 A

Max. 30 mΩ

Measurement range 5 A

Max. 10 mΩ

Electrical properties

Electrical isolation

Bus isolated from I/O power supply and digital inputs and outputs


Digital inputs and outputs isolated from each other

Operating conditions

Mounting orientation


Horizontal

Yes

Vertical

Yes

Installation elevation above sea level


0 to 2000 m

No limitation

>2000 m

Reduction of ambient temperature by 0.5°C per 100 m

Degree of protection per EN 60529

IP20

Ambient conditions

Temperature


Operation


Horizontal mounting orientation

0 to 60°C

Vertical mounting orientation

0 to 50°C

Derating

See section "Derating".

Storage

-40 to 85°C

Transport

-40 to 85°C

Relative humidity


Operation

5 to 95%, non-condensing

Storage

5 to 95%, non-condensing

Transport

5 to 95%, non-condensing

Mechanical properties

Note

Order 2x terminal block X20TB12 separately.
Order 2x screw clamp terminal block TB3102 and 2x screw clamp terminal block TB3104 separately.

Pitch

87.5+0.2mm


Product Photo




More Products



X20PS9600X20SO6300X20DC4395
X20CP0483X20SLX210X20BT9100
X20CP1483X20DI4371X20DI9371
x20cp1586X20BM05X20AT6402
X20CP1583X20BC0083X20AI4622
X20CP3584X20BC8083x20at4222
X20CP3583X20BB80x20bt9400
X20CP1585X20BM11X20AT2222
X20CP1584X20TB12X20AO4622
X20CP1684X20IF1072X20DO9322
X20CP1382X20DO6322X20IF1030
X20AI1744X20DC2395X20IF1082-2
X20DI6371X20BM15X20IF371
X20DOF322X20DO4332X20CM4810
X20DS4389X20DO4322X20AI83211
X20PS2100X20MM2436X20DOF322
X20PS9400X20DO8332X20PS3330
X20CS1030X20DC11A6X20BM01
X20CS1020X20CM8281X20SI9100
X20ATC402X20BR9300X20SI4100

Cooperative Brand



(DCS)

ABB / TRICONEX / FOXBORO/ I/A / HONEYWELL / TDC2000/3000 / YOKOGAWA / BENTLY NEVADA

(PLC)

B&R / ALLEN BRADLEY / BECKHOFF / HONEYWELL / OMRON / SIEMENS

(SENSOR)

IFM / SICK/ P+F/ WENGLOR / BAUMER / LEUZE / HOLLY/ SYSHOKUYO / EUCHNER

(CONNECTOR)

HARTING / PHOENIX CONTACT/ WEIDMUELLER

(VALVE)

SMC / FESTO / +GF+.......

(INSTRUMENT)

+GF+ /E+H / HITACHI / ROSEMOUNT


Why Choose Us



Xiamen ZhiCheng Automation Technology Co., Ltd it is a leading global supplier of control system components. We specialize in control systems and drives. With many years of experience in the industrial sector, we consistently deliver the highest quality of spare parts. We have tens of thousands of spare partsand spare parts warehouse . Products and services to serve for installing of users control system,Distributed control systems, programmable controllers, panel controller and drive!


We major in DCS system,Sensor,PLC,Connector,Valve, and Instrument,MAGNETRON,RO Membrane. With many years of experience in the industrial sector, we consistently deliver the highest quality of spare parts.which make sure that all this jobs are perfectly. If you have any further questions, please don't hesitate to contact us.


How To Contact Me



China X20CM0985 | B&R | Analog inputs X20 energy measurement and synchronization module supplier

X20CM0985 | B&R | Analog inputs X20 energy measurement and synchronization module

Inquiry Cart 0