Portable Energy Meter Test Bench

Brand Name:GENY
Certification:ISO, CE
Model Number:YC99T
Minimum Order Quantity:1 pcs
Delivery Time:4~6weeks
Payment Terms:T/T,L/C,D/P,T/T
Contact Now

Add to Cart

Verified Supplier
Location: Guangzhou China
Address: ROOM 107, 1ST FLOOR, No. 602 GUANGSHAN ER ROAD, TIANHE DISTRICT, GUANGZHOU, CHINA POSTCODE: 510663
Supplier`s last login times: within 32 hours
Product Details Company Profile
Product Details

Description



• YC99T Series Portable Three-Phase Meter Test System laboratory-grade accuracy in a rugged, field-ready package.

• YC99T-3C – IEC-protocol compliant for fully automated demand-error, tariff-switch, and time-of-use energy testing; built-in 0.05 ppm OCXO for daily clock-error verification.
• YC99T5C – identical software suite as the 3C with alternative voltage/current ranges to suit varied applications.
• Integrated harmonic source: programmable 2nd–21st order, stable output for harmonic influence tests.
• Ergonomic front-and-rear panels enable single-operator hook-up in under one minute.
• Lightweight, corrosion-resistant enclosure—precision lab performance wherever you need it.



1. The error of voltage, current, active power is ±0.05%, the error of reactive power is ±0.1%

2. The stability of voltage, current, active power is 0.01%RG/3min, The distortion percentage of alternative voltage and alternative current : ≤0.2%

3. The voltage range of YC99T-3C from 57.7V-660V, current range:1A-50A

4. Harmonic Output range: 2-63, harmonic output is under measuring and analyzing.

5. Test data can be managed by computer via RS232 interface

6. YC99T-3C not only can be operated by equipment but also can be controlled by PC

7. Calibrate energy meters automatically, which including items, such as, preheating, starting, creeping, error, influence, quantity test etc.

8. MUTs can be accessed through RS485, RS232, and Ethernet.

9. Diagnostic function of functional fault and internal module communication.



Specifications



Voltage

AC Voltage Range

57.7V-660V

Power of the voltage output

MAX.20VA

Resolution

0.01%

Accuracy

0.1%

Stability

0.01%/120s

Distortion factor

0.2%

Current

Test current output

1A-50A

Power of the current output

Max. 50VA

Resolution

0.01%

Accuracy

0.05%

Stability

0.01%/180s

Distortion factor

< 0.3% for linear resistance load

Phase angle

Range

0 -- 360°

Resolution

0.1°

Accuracy

0.2°

Frequency

Range

40Hz – 70Hz

Resolution

0.005Hz

Pulse output

Harmonic Output

2-63

Pulse input

Input channel

3

Input frequency

Max. 20Hz

Other

Voltage Supply

220V±15% /110V±15% (optional)

Ambient temperature

20°C -- 30°C

Relative humidity

≤85%

Dimensions (W×H×D) (mm)

500 X 440 X 180

Weight (kg)

26


China Portable Energy Meter Test Bench supplier

Portable Energy Meter Test Bench

Inquiry Cart 0