Technical Data



Technical spec.YC1893D-6YC1893D-12YC1893D-24YC1893D-48
Number of meter positions6122448
Accuracy0.05 / 0.02
Power SourceYCS-103-250YCS-103-600YCS-103-1200YCS-103-2500
Standard MeterSZ03A-K6 / SZ03A-K8
Scanning HeadYCG-S Series
Voltage
Test voltage output(Phase-Neutral)3x(24V~288V)(or customized)
Power of the voltage outputMax. 3x100VAMax. 3x250VAMax. 3x500VAMax. 3x1000VA
ResolutionBetter than 0.01% of full scale value of range
Setting accuracyBetter than 0.05% at the final range value
StabilityBetter than 0.005% /h (integration time 150s)
Load regulation from 0~max. loadBetter than 0.01%
Distortion factorBetter than 0.3% for linear resistance load
Harmonic2nd~21st free programmable
Current
Test current output3x(1mA~100A)
Power of the current outputMax. 3x150VAMax. 3x350VAMax. 3x750VAMax. 3x1500VA
ResolutionBetter than 0.01% of full scale value of range
Setting accuracyBetter than 0.05% at the final range value
StabilityBetter than 0.005% /h (integration time 150s)
Load regulation from 0~max. loadBetter than 0.01%
Distortion factorBetter than 0.3% for linear resistance load
Harmonic2nd~21st free programmable
Phase angle
Range0~360⁰
Resolution0.01⁰
Setting accuracy0.1⁰
Frequency
Range45Hz~65Hz
Resolution0.01Hz
Error display
Type of error displayRed LED
Resolution of error displays8 digitals
Other
Voltage supply3x220/380V±10%(or customized)
50/60Hz ±2Hz
Ambient temperature-10°C~+40°C
Relative humidity35%~85%



Description:


1. The meter test system is capable of testing mechanical meters, electronic mechanical meters and electronic meters by automatic, semi-automatic or manual operation.
2. Meters to be tested: 3P4W, 3P3W, 1P2W.
3. Test modes: active power, reactive power and cross-connected reactive power.
4. It can simultaneously measure meters with the same specifications but different meter constants.
5. It automatically positions the rotor mark of the mechanical meter disc, improving efficiency.
6. It performs start-up and creep tests.
7. Neutral current test (optional).
8. The installation of an ICT in each meter position makes it possible to test three-phase meters with closed connections between the current and voltage measuring circuits (I-P connections) (optional).
9. Protection functions against overload, short-circuit voltage and open-circuit current.
10. The synchronised movement of the scanning heads simplifies control.
11. Made of aluminium alloy, it is light, strong and corrosion resistant.
12. The test software, which is compatible with Windows 2000/XP/7/8/10, includes function modules for various modern energy meters, enabling real fault testing, harmonic testing, demand testing and influence testing, etc.



Applications:



1. Utilities at the national level
2. State metrology offices
3. Large energy meter manufacturers



Primary competitive advantages:



1. High quality product
2. Over 18 months warranty
3. High accuracy class: 0.05/0.02
4. Can be customised by three phase electric energy meter test bench
5. Extremely high power stability
6. Neutral current test (optional)
7. Timing fault test
8. Voltage, frequency and harmonic distortion test
9. Installation of RS232, Ethernet communication port in each meter position.
10. Tilt impact test (optional)