Powerful Stationary Meter Test System for Testing Voltage Current and Power Capacity

Brand Name:GENY
Certification:ISO, CE
Model Number:YC-1893R
Minimum Order Quantity:1
Delivery Time:6~8weeks
Payment Terms:T/T, L/C, D/P, T/T
Contact Now

Add to Cart

Verified Supplier
Location: Guangzhou China
Address: ROOM 107, 1ST FLOOR, No. 602 GUANGSHAN ER ROAD, TIANHE DISTRICT, GUANGZHOU, CHINA POSTCODE: 510663
Supplier`s last login times: within 32 hours
Product Details Company Profile
Product Details

Powerful Stationary Meter Test System for Testing Voltage Current and Power Capacity

Technical Parameter

Power Supply / Electrical System


Voltage240/415 V AC supply (+5% & -10%) or customized
Frequency50/60Hz ±2Hz
Power capacity> 3 × 6kVA
Ambient temperature-10°C … +40°C
Relative humidity35% … 95%
System GroundingNeutral solidly grounded
Surge protection level≥ 10 kV/120 Joules (10/1000µs)

Power source


Voltage
Test voltage output (Phase-Neutral)3× (24V – 500V) or customized
Power of the voltage output3×100VA
ResolutionBetter than 0.01% of full scale value of range
Setting accuracyBetter than 0.05% at the final range value
StabilityBetter than 0.005%/h (integration time 150 s)
Load regulation from 0-max. load< 0.01%
Distortion factor< 0.3% for linear resistance load
Harmonics2nd – 21st free programmable
Current
Test current output3× (1mA – 120A)
Power of the current output3×150VA
ResolutionBetter than 0.01% of full scale value of range
Setting accuracyBetter than 0.05% at the final range value
StabilityBetter than 0.005%/h (integration time 150 s)
Load regulation from 0-max. load< 0.01%
Distortion factor< 0.3% for linear resistance load
Harmonics2nd – 21st free programmable
Phase angle
Range0 -- 360°
Resolution0.01°
Setting accuracy0.1°
Frequency
Range45Hz – 65Hz
Resolution0.01Hz

Reference Standard


Power supply
VoltageAC220V ±10%
Frequency50Hz ±2Hz
Max power consumption45VA
Using condition
Environment temperature10ºC … 30ºC
Relative humidity45% … 75%
Outside magnetic intensity≤ 0.025mT
Frequency range45Hz … 65Hz
Test current
Range1mA … 120A
Error

- ±0.02% (50mA…120A) (relative measurement value)

- ±0.05% (1…50mA) (relative range full-scale value)

Current display range1.000mA … 120.000A (1A, 10A, 100A)
Test voltage
Range50V … 480V (auto range)
Error

- ±0.02% (50V…480V) (relative measurement value)

- ±0.05% (5V…50V) (relative measurement value)

Voltage display range50.000(V) … 480.000(V)
Power measure error
Active power+0.02% (relative measurement value) 50V … 480V, 0.05A … 120A
Reactive power+0.05% (relative measurement value) 50V … 480V, 0.05A … 120A
Apparent power+0.05% (relative measurement value) 50V … 480V, 0.05A … 120A
Test Power Factor(PF=P/F) Error: 0.05%
Display range-1.00000 … +1.00000
Energy constant

CH=109 imp/kWh (1A & 0.1A step)

CH=108 imp/kWh (10A step)

CH=107 imp/kWh (100A step)

Measuring modes

- 4 wire active/ reactive/ cross-connect reactive

- 3 wire active/ reactive/ cross-connect reactive

- 2 wire active/ reactive


Energy pulse input
Frequency0.5kHz
Voltage24V
Measurement range of input
OutputTTL pulse, load > 2kΏ
Dimensions (W * H * D)131mm * 432mm * 470mm
Weight16kgs

Features and functions

The MTS have features as below

- Supporting parallel communication port to test smart meters through RS232 / Ethernet

- Calibrating terminals on the rack for test bench verification

- 1-phase energy meter for testing

- 3-phase energy meter for testing

- Accuracy Testing of reference standard meter

- Pre-warming

- Accuracy test as per IEC

- Creeping test

- Starting current test

- Repeatability of error test

- Dial test

- Influence quantity test related to accuracy tests (Voltage, Frequency, reverse phase sequence, voltage unbalance)

- Influence of harmonic component in voltage and current circuit as per IEC

- Tamper and Fraud Monitoring

- Sub Harmonics as per IEC standards (IEC 62052-11 / 62053-21/22/23)

- Odd Harmonics as per IEC standards

China Powerful Stationary Meter Test System for Testing Voltage Current and Power Capacity supplier

Powerful Stationary Meter Test System for Testing Voltage Current and Power Capacity

Inquiry Cart 0