FGI 6kV~6.6kV Indoor Type Static Var Generator – Advanced Power Quality & Grid Stability

Place of Origin:China
Contact Now

Add to Cart

Verified Supplier
Location: Jincheng Shandong China
Address: Jincheng Road,Economic Development Zone,Wenshang,Shandong
Supplier`s last login times: within 31 hours
Product Details Company Profile
Product Details

FGI 6kV~6.6kV Indoor Type Static Var Generator – Advanced Power Quality & Grid Stability


Features & Functions


  • Extreme Ride-Through:

Our SVG quickly restores normal operation after grid voltage dips or surges, adapting to various grid conditions without manual intervention.

  • Voltage Fluctuation Suppression:

For fluctuating loads like arc furnaces, our SVG dynamically provides reactive current to quickly stabilize voltage and suppress flicker.

  • Reliable Dual Power:

The control system features a dual power supply (380VAC/220VAC or 220VDC) with seamless online backup switching, ensuring continuous operation even if one source fails.

  • EMC Compliant Enclosure:

Our cabinet boasts an anti-interference design, passing rigorous EMC tests for robust performance in challenging electromagnetic environments.

  • Redundant & Stable System:

Options for a dual-master control system and automatic bypass for power units ensure high availability and stable operation, even with component faults.


Dimensions


6~6.6kV Static Var Generator(SVG) – Indoor type
Heat-dissipating methodVoltage class(kV)Rated capacity(Mvar)

Dimension

W*D*H(mm)

Weight(kg)Reactor type
Liquid cooled6~6.61.0~15.05800*2438*25917900~8900Air core reactor
Air cooled1.0~6.05200*2438*25606500Iron core reactor
7.0~12.06700*2438*25606450~7000Air core reactor

Applications

1. Renewable energy integration in solar and wind farms, intermittent generation causes voltage fluctuations, SVG offers:

  • Injects or absorbs current in real time to stabilize voltage.
  • Improves power factor compliance with grid codes.
  • Enhances grid reliability, reducing voltage flicker.

2. Industrial power quality management heavy industrial loads often lead to voltage drops and low power factors, SVG offers:

  • Dynamic current compensation, stabilizing voltage and improving power factor.
  • Reduced energy costs by minimizing reactive power penalties.
  • Enhanced equipment protection by preventing voltage dips.

3. Grid and Transmission Line Stability In long-distance power transmission, SVG offers:

  • Voltage stability during load variations.
  • Power factor regulation, reducing line losses.
  • Grid reliability by preventing voltage collapse.

Returns & Benefits


  • Stabilize the Grid, Avoid Penalties:

Correct power factor, stabilize voltage, and reduce grid impact to prevent fines and failures caused by power quality issues.

  • Boost Power Generation, Increase Revenue:

Lower line losses and optimize inverter efficiency to significantly enhance the power output of your photovoltaic (PV) stations.

  • Optimize Quality, Extend Lifespan:

Suppress harmonics and improve overall power quality, leading to reduced equipment damage, extended operational life, and lower maintenance costs.

  • Expand Grid Connection, Increase Output:

In areas with limited grid capacity, enhance your PV station's grid integration capability to maximize power generation.


Technical Specifications


NameSpecification
Rated voltage6kV±10%6.6kV±10%
Assessment point voltage

6kV±10%6.6kV±10%

Input voltage0.9~ 1.1pu; LVRT 0pu(150ms), 0.2pu(625ms)
Frequency50/60Hz; Allow short-term fluctuations
Output capacity±0.1Mvar~±200 Mvar
Starting power±0.005Mvar
Compensation current resolution0.5A
Response time<5ms
Overload capacity>120% 1min
Power loss<0.8%
THDi<3%
Control power380VAC, 220VAC/220VDC
Reactive power regulation modeCapacitive and inductive automatic continuous smooth adjustment
Communication interfaceEthernet, RS485, CAN, Optical fiber
Communication protocoModbus_RTU, Profibus, CDT91, IEC61850- 103/104
Running modeConstant device reactive power mode, constant assessment point reactive power mode, constant assessment point power factor mode, constant assessment point voltage mode and load compensation mode
Parallel modeMulti machine parallel networking operation, multi bus comprehensive compensation and multi group FC comprehensive compensation control
Protection

Bus overvoltage, bus low voltage, SVG overcurrent, drive fault, module overvoltage, overcurrent, overtemperature and

communication fault; Protection input interface, protection output interface, abnormal system power supply and other protection functions.

Fault handlingAdopt redundant design to meet N-2 operation
Cooling modeWater cooling/Air cooling
IP degreeIP30(indoor); IP44(outdoor)
Storage temperature-40℃~+70℃
Running temperature-35℃~ +40℃
Humidity<90% (25℃), no condensation
Altitude<=2000m (above 2000m customized)
Earthquake intensityⅧ degree
Pollution levelGrade IV

Selection Guide

SVG Selection:

  • Indoor or Outdoor: Determine if the installation requires an indoor or outdoor unit based on site conditions.
  • Capacity Assessment: Evaluate the necessary capacity based on site requirements.
  • Special Function Requirements: Identify any specific functional needs (e.g., advanced harmonic filtering, flicker mitigation).
  • Cooling Method: Choose between air-cooled or liquid-cooled systems depending on the site environment and specific conditions.

Industry Applications:

  • Traditional Industries: Primarily used for power factor correction.
  • New Energy Applications: Typically sized based on the power generation capacity.





Production Base: Jincheng Road, Economic Development Zone, Wenshang County, Jining City, Shandong Province, China


Email: overseas@fengguang.com


Website: www.fengguang.com


China FGI 6kV~6.6kV Indoor Type Static Var Generator – Advanced Power Quality & Grid Stability supplier

FGI 6kV~6.6kV Indoor Type Static Var Generator – Advanced Power Quality & Grid Stability

Inquiry Cart 0