What is the RIA15 process indicator?
- The RIA15 is a loop-powered local display (process indicator) designed to
show process signals (e.g. 4-20 mA) in the field or on a panel.
- It can also support HART® communication to display additional sensor variables (up to four)
when connected to HART-capable devices.
- It is often used where you want a local read-out of an analog loop
without needing a full controller or separate power supply.
Key specifications & features
Here are some of the notable technical and functional features of
the RIA15:
Feature | Description |
Input signal | 1 × analog 4-20 mA (scalable) |
HART support | Yes — can act as a primary or secondary HART master, read and
display up to 4 HART variables (PV, SV, TV, QV) |
Powering | Loop-powered; no separate external power supply required |
Voltage drop in loop | ≤ 1 V (for standard 4-20 mA mode) / ≤ 1.9 V (if using HART) |
Display | 5-digit LCD (digit height ~17 mm) + bar graph; backlight option |
Housing / mounting | Available in panel mount or field (weatherproof / explosion-proof)
versions |
Configuration / operation | 3 front keys for menu navigation & parameter setting; can be
locked via passcode |
Approvals / safety | Various certifications (ATEX, IECEx, FM, CSA, etc. depending on
version) |
Functional safety (SIL, safety use) | Some versions are “LA” type / SIL-certified. The device’s safety
function is the faithful transmission of the 4-20 mA signal without
distortion; the display is not part of the safety function. |
How it works / modes of operation
- In its standard analog mode, the RIA15 is inserted into the current
loop (4-20 mA) and it measures the current, converts it to the
configured engineering units, then displays that value locally.
- In HART mode, the device can poll the sensor via the HART protocol
and fetch additional variables (e.g. temperature, pressure,
diagnostics) to display.
- It can be either primary or secondary HART master. In a HART loop, typically there is one primary master
(e.g. DCS / PLC) and optionally a secondary master (such as the
RIA15) for local diagnostics
- The display can alternate among different HART variables based on
configuration (e.g. PV → SV → TV → QV).
Use cases & advantages
- Local readout: Offers a way to visualize the loop’s process value right where
the measurement is, without needing a full controller or remote
display.
- Low voltage drop: Because it introduces very little voltage drop (≤ 1 V or ≤ 1.9 V
in HART mode), it is suitable even when the loop supply voltage is
tight.
- HART diagnostics: If your sensor is HART-enabled, you gain access to additional
information (status, diagnostics, extra variables) via the
indicator.
- Flexibility: It can be panel-mounted or used in the field, and is configurable
on-site with minimal tools.
- Safety use: Where applicable, “LA” versions allow using the indicator as part
of a safety instrumented system (SIS), with restrictions and proper
proofs/tests.
Company Profile
Xi'an Xiyi Central Control Technology Co., Ltd. is an enterprise
engaged in the production, sales and R & D of industrial automation
instruments. The company is located in the ancient city of Xi'an, a
prosperous international city in China.
The company is mainly engaged in Rosemount and Yokogawa pressure
transmitters, differential pressure transmitters, liquid level
transmitters, temperature transmitters, mass flow meters and vortex
flow. Thermocouple, thermal resistance (armored, explosion-proof,
high temperature resistant, corrosion resistant, etc.), pressure
gauge, pressure gauge and bimetal thermometer. And Shanwu avp100 /
avp300 valve positioner, abb valve positioner, Siemens valve
positioner, YT valve positioner, Koso valve positioner, Shanwu
regulating valve and other products. The company has a strong
management team and brings together advanced technical talents at
home and abroad, which will provide you with better service.