XZH TEST Digital Portable Transformer on-Load Tap-Changer Tester Fast and Accurate
The on-load tap-changer is the only moving part that is connected
to the transformer circuit, so the detection of the on-load
tap-changer is getting more and more attention. In the "Procedures
for Handling and Preventive Tests for Electrical Equipment", it is
required to check the sequence of actions and the switching time of
the on-load tap-changer.
The XHYZ1668A transformer on-load tap-changer tester is mainly used
to measure the transition waveform, transition time, transient
resistance value, and three-phase synchronization of the on-load
tap-changer.
1. The instrument has large output current and its weight is light;
2. Two-stage current output, wider test range and higher stability;
3. Can automatically calculate the transition resistance value and
transition time;
4. It has perfect protection circuit and strong reliability;
5. 5.7-inch large LCD display, it's easy for on-site operation;
6. U disk storage function, can store more waveforms data .
7. The keyboard and one-button shuttle are operated independently,
which makes the instrument more convenient to operate.
Output current | 1.0A,0.5A,0.2A |
Test range | Transition resistance: 0.3Ω~20Ω(1.0A) 5Ω~40Ω(0.5A) 20Ω~100Ω(0.2A) Transition time: 0~320ms |
Open circuit voltage | 24V |
Test accuracy | Transition resistance: ± (5% reading ±0.1Ω) Transition time: ± (0.1% reading ±0.2ms) |
Sampling rate | 20kHz |
Storage mode | local storage |
Ambient temperature | -10 ° C ~ 50 ° C |
Ambient humidity | ≤85%RH |
Working power supply | AC220V±10% |
Power frequency | 50±1Hz |
Size | host: 360*290*170 (mm) wiring box:360*290*170(mm) |
Weight | host 6.15KG , wiring box4.55KG |