Add to Cart
XHHV515-8L
The XHHV515-8L High voltage pulse generator is a tie-rod portable integrated device, which is mainly used for shock discharge during low-voltage cable fault testing. The pulse generator adopts humanized design operation mode, high-precision dedicated high-voltage electronic components and high-frequency high-voltage technology, which is easy to operate, light in weight and easy to carry.
It integrates the energy storage capacitor, DC high voltage source, and discharge ball gap. The operation of this equipment is safe and reliable, with automatic protection functions of over-current, overvoltage and overheating, it can truly achieve the effect of not being damaged by impact, and it can also work normally with high voltage to ground.
The XHHV515-8L high voltage pulse generator is equipped with a time relay, and the discharge time interval can be arbitrarily set within 0-100 seconds. When working, the high-voltage pulse output is uniform and controllable, high-voltage side voltage measurement, make the result real-time and accurate. Unique high-voltage measurement design, in the stop state, the voltmeter can indicate the capacitor voltage in real time. The user can observe the residual voltage while discharging, until the voltage value returns to zero, and finally make the discharge more thorough.
Panel introduction
Panel function description
1. Safety ground: The ground of the instrument shell must be reliably connected to
the ground in order to prevent the instrument shell from being
electrified or to personnel.
2. High-voltage ground: Also known as high-voltage tail, it must be grounded reliably to
prevent high-voltage leakage and discharge. Poor contact may cause
failure to boost the voltage, high voltage breakdown of the
internal components of the instrument, and safety accidents caused
by leakage or discharge inside the instrument.
3. Sampling ground: The negative terminal of the pulse energy storage capacitor has a
high voltage and must be grounded reliably. It is used for sampling
when the waveform is sampled under the high-voltage flashover state
of the cable fault tester. (WithoutHigh voltage surge generator
high-voltage flashover sampling, reliable grounding is still
required).
4. Discharge button: Press this button to make contact with the ball gap, and discharge
manually. (The duration of each key press cannot exceed 1s).
5. High voltage start button: When the start button light is on, it means that the voltage
output is in the zero position. When the light is on, the start
button is valid. If the start button light is not on after turning
on the power switch, turn the voltage adjustment knob
counterclockwise until the light is on. When the button light is
on, press this button to start the device and generate high voltage
output.
6. High-voltage stop button: When the test is completed or an abnormality occurs, press this
button to cut off the high-voltage output, the high-voltage light
goes out, and the internal discharge ball stops working. When the
stop key is on, it means there is
high voltage output, and when it is off, it means there is no high
voltage output.
7. Over-current protection switch: When pressed, it means that the over-current protection function
has started; when it is popped up, it means that the instrument has
triggered the over-current protection.
8. Voltage adjustment: After turning on the device, you must first turn the knob
counterclockwise to the end, press the start button, and then
adjust clockwise to increase the output high voltage from small to
large, and adjust counterclockwise to
reduce the output high voltage from large to small.
9. Power switch: "I gear" turns on the AC 220V power supply switch, and "0 gear"
turns off the system power.
10. The fuse holder: the place where the fuse of the AC 220V power supply system is
installed.
11. Power socket: the working power supply of the instrument, AC 220V connection
port.
12. Time setting: Set the discharge time interval.
13. Ammeter: indication of the current on the high voltage side.
14. Voltmeter: high voltage output voltage indicating kV meter.
15. High-voltage output (EMP): When impacting discharge, connect the high-voltage output line.
16. High voltage output (DC): When DC withstand voltage, connect the high voltage output line.
Technical parameters
Impact high voltage | 0~15kV |
High voltage partial pressure | 2.5 level |
Built-in capacitor | 8μF |
Discharge power | 0-900J |
Output voltage polarity | negative polarity |
Impact power | 400W |
Working mode | Selectable or adjustable impulse rate and Single shot |
Minimum Output current in DC mode | 16mA at 15kV |
Length of test cables | The high-voltage output line of the pull-rod type high-voltage pulse generator is 2 meters long, the ground line is 3 meters long, and the power line is 1.8 meters long. |
Over temperature protection | 65℃ |
Over current protection | 8mA (more than 3 seconds) |
Volume(mm) | 540L×300W×450H |
Weight | not more than 25kg |
Power supply | AC220V±15%, 50Hz±2Hz(60Hz) |
Ambient temperature | -20~+60℃ |
Packing List
Onsite test case