MTL4041B MTL Instruments Repeater Power Supply

Brand Name:MTL
Certification:HART
Model Number:MTL4041B
Minimum Order Quantity:1
Delivery Time:stock
Payment Terms:T/T
Contact Now

Add to Cart

Verified Supplier
Location: Hong kong China
Address: RM 509, 5/F, THE CLOUD, 111,TUNG CHAU STREET, TAI KOKTSUI, KOWLOON,HONG KONG
Supplier`s last login times: within 48 hours
Product Details Company Profile
Product Details

MTL4041B MTL Instruments Repeater Power Supply

MTL Instruments MTL4041B Repeater Power Supply provides a fully floating dc supply for energizing a conventional 2- or 3-wire 4/20mA transmitter or a 'smart' transmitter located in a hazardous area, and repeats the current in another circuit to drive a safe-area load. For smart transmitters, the unit allows bi-directional transmission of digital communication signals superimposed on the 4/20mA signal so that the transmitter can be interrogated either from the operator station or by a hand-held communicator (HHC). The module can also be used with hazardous area current sources and some vortex and turbine meters.

  • Product type : Repeater Power Supply

  • 4/20mA, smart, for 2- or 3-wire transmitters

  • The MTL4041B provides a fully floating dc supply for energising a conventional 2- or 3-wire 4/20mA transmitter or a smart transmitter located in a hazardous area, and repeats the current in another circuit to drive a safe-area load.

  • Number of channels: One

  • Location of transmitter: Zone 0, IIC, T4 6 hazardous area if suitably certified

  • Div.1, Group A, hazardous location

  • Voltage available for transmitter and lines : 15V minimum at 20mA

  • Note: maximum open-circuit voltage is 28V

  • Input and output signal range : 4 to 20mA

  • Over-/under-range: 1.0mA to 21.5mA

  • Digital signal bandwidth: 10Hz to 8kHz

  • Safe-area circuit load resistance: Conventional transmitters: 0 to 650 Smart transmitters: 250 ±10%

  • Safe-area circuit output resistance: >1M

  • Safe-area circuit ripple: <50µA peak-to-peak up to 80kHz

  • Transfer accuracy at 20°C: Better than 20µA

  • Temperature drift: <1µA/°C

  • Response time: Settles within 200µA of final value within 20ms

  • LED indicator Green: one provided for power indication

  • Power requirement, Vs: 65mA at 24V dc/ 75mA at 20V dc/ 50mA at 35V dc with 20mA signal

  • Power dissipation within unit: 1.2W at 24V with 20mA signal/ 1.4W at 35V

  • Isolation : 250V ac between safe- and hazardous-area circuits