Add to Cart
1.5kV DC PV Solar Cable Climate Resistance H1Z2Z2-K
The cable is designed for connecting photovoltaic system components inside and outside of buildings and equipment with high mechanical requirements and extreme weather conditions.It has the characteristics of Climate resistance, UV resistance,aging resistance,and the service life is over 25years.
Conductor: Using multiple tin-plated soft copper wire stranded into insulation
Insulation: Irradiation low smoke halogen-free flame retardant XLPE
Sheath: Halogen free flame-retardant sheath material for photovoltaic cables
Properties such as moisture and heat resistance, high and low temperature resistance, acid and alkali resistance,ozone resistance, UV resistance, flame retardancy, etc
AC rated voltage(U0/U):1.0/1.0kV
DC rated volate(U0):1.5kV
Maximum operating temperature of conductor:+ 120℃
Environmental temperature for use:- 40C~+90℃
Cable laying temperature: not less than -25 ℃
Pipe laying, shallow trench laying, cable trench laying, tunnel laying, interlayer laying, supported overhead laying, suspended overhead laying, etc.
Cross section(mm²) |
Conductor Construction(no/mm) |
Conductor Stranded OD.max(mm) |
Cable OD.(mm) |
Approximate weight of cable |
Max Cond Resistance(Ω/km,20°C) |
1×1.5 |
48/0.20 |
1.58 |
4.8 |
35 |
13.7 |
1×2.5 |
77/0.20 |
2.02 |
5.2 |
47 |
8.21 |
1×4 |
56/0.285 |
2.46 |
5.7 |
64 |
5.09 |
1×6 |
84/0.285 |
3.01 |
6.3 |
86 |
3.39 |
1×10 |
77/0.40 |
4.1 |
7.2 |
128 |
1.95 |
1×16 |
7×17/0.40 |
5.5 |
8.9 |
196 |
1.24 |
1×25 |
7×27/0.40 |
6.7 |
10.7 |
299 |
0.795 |
1×35 |
7×38/0.40 |
8.2 |
12.4 |
407 |
0.565 |
1×50 |
19×20/0.40 |
10.0 |
14.6 |
571 |
0.393 |
1×70 |
19×28/0.40 |
11.6 |
16.4 |
773 |
0.277 |
1×95 |
19×38/0.40 |
13.5 |
18.5 |
1024 |
0.210 |
1×120 |
24×38/0.40 |
14.4 |
19.8 |
1266 |
0.164 |
1×150 |
30×38/0.40 |
16.2 |
22.2 |
1584 |
0.132 |
1×185 |
37×38/0.40 |
18.2 |
25.0 |
1967 |
0.108 |
1×240 |
48×38/0.40 |
20.6 |
27.8 |
2518 |
0.0817 |
Installation method |
Single cable in air |
Single cable on object surface |
Two contacting cables on object surface |
Cross section(mm²) |
Carrying capacity(A) |
||
1.5 |
30 |
29 |
24 |
2.5 |
41 |
39 |
33 |
4 |
55 |
52 |
44 |
6 |
70 |
67 |
57 |
10 |
98 |
93 |
79 |
16 |
132 |
125 |
107 |
25 |
176 |
167 |
142 |
35 |
218 |
207 |
176 |
50 |
276 |
262 |
221 |
70 |
347 |
330 |
278 |
95 |
416 |
395 |
333 |
120 |
488 |
464 |
390 |
150 |
566 |
538 |
453 |
185 |
644 |
612 |
515 |
240 |
775 |
736 |
620 |
Operation temperature |
120℃ |
||
Ambient temperature |
60℃ |
Correction and Adjustment Factors
Ambient temperature(℃)(air) |
≦60 |
70 |
80 |
90 |
100 |
110 |
Correction factor |
1 |
0.91 |
0.82 |
0.71 |
0.58 |
0.41 |